3.20 INFO menu

Press button 3 from the initial display screen to see a
series of information items relating to boiler operation,
listed according to the parameter name and value.
To switch between parameters, press the
buttons. Press
to see the selected parameter; press
to return to the main screen.
PARAMETER
NAME
I001
Screed heater hours
I002
Flow sensor
I003
Return probe
I004
Domestic hot water probe
I006
Low storage tank probe
I007
Collector temp
I008
Flue gas probe
I009
Outdoor temperature sensor
I010
External temp. for temperature control Filtered outdoor temperature sensor value used in the temperature control algorithm to calculate the heating setpoint
I011
DHW fl ow rate
I012
Fan rotations
I013
Flow sensor (main zone)
I014
Flow sensor (zone 1)
I015
Flue gas probe meter
I016
Delivery setpoint (main zone)
I017
OT+ heating setpoint
I018
System pressure
I019
DHW hours
I020
CH hours
I021
% DHW modulation
I022
% CH modulation
I023
Average heating fl ow probe
I024
Average DHW fl ow probe
I025
Average heating return probe
I026
Average DHW return probe
I027
Number cycles ON EVG
I028
Ionisation current
I029
High effi ciency mode
I033
Board ID
I034
Board fw rev
I035
Interface fw rev
I039
Alarm log 1 (oldest)
I040
Alarm log 2
I041
Alarm log 3
I042
Alarm log 4
I043
Alarm log 5 (most recent)
I044
No. of days for CFS

3.21 Temporary switch-off

In the event of temporary absences (weekends, short
breaks, etc.) set the status of the boiler to OFF
The electricity supply and fuel supply remain active, so
the system is protected by:
ƒ heating anti-freeze: this function is activated if the
temperature measured by the flow sensor drops be-
low 5°C. A heat request is generated in this phase,
with burner ignition at minimum output and main-
tained at this level until the delivery water tempera-
ture reaches 35°C;
and
DESCRIPTION
Number of hours of screed heater operation (when function in progress)
Boiler fl ow sensor value
Boiler return temperature sensor value
Value of high storage tank probe
Value of low storage tank probe (if a solar storage cylinder is installed)
Solar collector probe value (case C and solar system present)
Flue gas probe value
Instantaneous outdoor temperature sensor value
DHW setpoint only with OT+ connection
Number of fan rotations (rpm)
Main zone fl ow sensor value (when P4.12 = 1)
Zone 1 fl ow sensor value (when 1 P4.23 = 1)
Number of operating hours of the heat exchanger in "condensing mode" (the values, in thousands, are
visualised/100
Main zone delivery setpoint
Heating setpoint sent to the boiler from the OT+ remote control
System pressure
This counter measures the burner "ON" time (fl ame presence) in DHW mode, value expressed in seconds
Hours burner on in heating
This counter measures the average modulation percentage (ID17) when burner on in DHW
Average percentage value of modulation with burner on in heating
Average fl ow probe values with burner on in heating mode
Not used if parameter P3.01 = 0
Average return probe values with burner on in heating mode
Not used if parameter P3.01 = 0
Number of gas valve ON cycles
Instantaneous ionisation current detected by the detection electrode
Indicates when the high effi ciency mode is running
Electronic board identifi cation
Firmware revision of the electronic board
Firmware revision of the interface
List of the last 5 alarms recorded
Number of days that have elapsed since the CFS signal was activated (i.e. since EXPIRE P7.07 = 0)
ƒ DHW anti-freeze (if water tank with probe): this
function is activated if the temperature measured by
.
the water tank probe drops below 5°C. A heat request
is generated in this phase, with burner ignition at
minimum output and maintained at this level until
the delivery water temperature reaches 55°C.
9
The activation of the ANTI-FREEZE function is sig-
nalled by a sliding message on the interface dis-
play: AF1 (DHW ANTI-FREEZE IN PROGRESS) or AF2
(HEATING ANTI-FREEZE IN PROGRESS), depending on
the situation.
ƒ circulator anti-blocking: the circulator activates every
24 hours of stoppage for 30 seconds.