1.11
Water circuit
Condexa HPR 35-45
4 5
3
2
1
MI
Condexa HPR 55-70
9
5
4
8
3
2
1
MI
Key
RI Heating return line
MI Heating delivery line
1
Degassing unit tap/boiler discharge
2
Heating pressure switch
3
Pressure transducer
4
Flow sensor
5
Safety thermostat
6
Heat exchanger
7
Return probe
8
Pressure gauge
9
Air vent valve
10 Circulator
Probes in the boiler
1
2
6
3
4
Condexa HPR 35-45
7
8
9
10
Condexa HPR 55-70
RI
6
2
7
Resistive values of the NTC probes with variations in the
temperature
10
Temperature °C
Tolerance test ±10%
RI
13
Safety thermostat
NTC delivery probe
Flue gas probe
NTC return line probe
1
2
1
Resistance Ω
Tolerance test ±10%
-20
67523
-15
53254
-10
42291
-5
33808
0
27700
5
22290
10
18070
15
14740
20
12110
25
10000
30
8300
35
6924
40
5810
GENERAL REMARKS
3
4
3
4
Temperature °C
Resistance Ω
45
4896
50
4147
55
3525
60
3011
65
2582
70
2224
75
1922
80
1668
85
1451
90
1267
95
1110
100
975