Adjusting The Heating Water Temperature Without An Outdoor Temperature Sensor Connected (Only In The Case Of A Boiler With Sensor); Adjusting The Heating Water Temperature With An Outdoor Temperature Sensor Connected; Adjusting The Domestic Hot Water Temperature; Safety Stop - Riello Condexa HPR 35 Instructions For The Installer And For The Technical Assistance Centre

Table of Contents

Advertisement

3.6
Adjusting the heating water temperature
without an outdoor temperature sensor
connected
(only in the case of a boiler with
sensor)
If there is no outdoor temperature sensor, the boiler
works with a fixed point. In this case, the HEATING set-
point can be set from the main screen. Press button C
or D to see the current heating setpoint value; the value
will flash (0.5 sec ON, 0.5 sec OFF) and the
icons will light up.
+
RESET
Press button C or D again to set the heating setpoint val-
ue within the predefined range:
[40°C ÷ 80.5°C] for high-temperature systems
[20°C ÷ 45°C] for low-temperature systems
in steps of 0.5°C.
The level bars next to the heating icon show the setpoint
value in relation to the operating range:
- 4 bars activated = max setpoint
- 1 bar activated = min setpoint
If button C or D is pressed and held, the meter will alter
the set value more quickly. If no button is pressed for 5
seconds, the set value is taken as the new heating set-
point and the display returns to the main screen.
3.7
Adjusting the heating water temperature
with an outdoor temperature sensor
connected
If an outdoor temperature sensor is installed and
temperature control is enabled (parameter P4.18 = 1),
the delivery temperature value is automatically selected
by the system, which quickly adjusts the ambient
temperature according to the variations in the outdoor
temperature. If you want to change the temperature
value (increasing or reducing the value automatically
calculated by the electronic board), you can alter the
HEATING setpoint as follows:
Press button C or D and select the required level within
the range (-5 ÷ +5) (see paragraph "3.3 Setting the
temperature control" ).
Note: if an outdoor temperature sensor is connected,
the boiler can still work with a fixed point if you set pa-
rameter P4.18 = 0 (menu P4).
and
+
C
D
MENU
3.8 Adjusting the domestic hot water
temperature
CASE A: heating-only, with no storage tank - adjustment
not applicable
CASE B: heating-only + external storage tank with ther-
mostat - adjustment not applicable
CASE C: heating-only + external storage tank with probe
- to adjust the temperature of the DHW
held in the storage tank, proceed as follows:
from the main screen, press button A or B to see the cur-
rent DHW setpoint; the value will flash (0.5 sec ON, 0.5
sec OFF) and the
and
+
A
B
Press button A or B again to set the DHW setpoint, increas-
ing or decreasing it in steps of 0.5°C within the prede-
fined range. The level bars next to the heating icon show
the setpoint value in relation to the operating range:
- 4 bars activated = max setpoint
- 1 bar activated = min setpoint
3.9

Safety stop

In the event of ignition faults or boiler operating faults,
there will be a "SAFETY STOP". The display will show not
only the code of the fault but also the flashing
(0.5 sec ON, 0.5 sec OFF). The backlight will flash for 1
min, then switch off, whereas the
flashing. The 4-digit space will show a sliding message
containing the error code and a description.

3.10 Reset function

The RESET icon lights up in the event of an alarm that
needs to be manually reset by the user (e.g. a flame
lockout). To reset the lockout, press button 2 Reset.
If the release attempts do not restart the boiler, contact
your local Technical Assistance Centre.
39
COMMISSIONING
icons will light up.
+
RESET
MENU
icon will continue
DAY
DAY
RESET
icon