Table 6-4
6.6.1
Type of conductor connection
Terminal board
Connection with cable lug
DIN 46 234
Bend down the cable lug for the
connection.
Connection of an individual conduc‐
tor with terminal clamp
Connection of two conductors of
approximately the same thickness
with terminal clamp
①
Connecting bar
②
Line supply cable
③
Motor connecting cable
④
Cover plate
1LE1, 1FP1/3, 1PC1/3 shaft height 63 ... 315
Operating Instructions, 11/2023, A5E38483075A
Max. conductor connection
Shaft height
63 ... 90
100 ... 112
132
160 ... 180
200
225
250 ... 280
315
6.6 Conductor connection
Max. connectable conductor cross-section
[mm²]
1.5
2.5 with cable lug
4.0
6.0
16.0
25.0
35.0 with cable lug
120.0
240.0
Electrical connection
Conductor
cross-
section
[mm²]
... 25
... 10
... 25
73