Horizontal Left - Trane 2TEE3C31A1000A Installer's Manual

Convertiblevariable speedcommunicating air handlers 2 112- 5 ton
Hide thumbs Also See for 2TEE3C31A1000A:
Table of Contents

Advertisement

Installer's
Guide
Figure 8 Mounting Installation Options
for Horizontal Applications
HORIZONTAL LEFT
a.
b.
c.
For maximum
efficiency
and Customer
ease of
filter
maintenance,
it is recommended
that
a
properly
sized remote
filter
and grille be in-
stalled
for horizontal
applications.
Airflow should
not exceed the face velocity
of the filter
being
used.
The
factory
installed
filter
should
then
be removed
from
the unit.
To convert
the unit to horizontal
left, front
ac-
cess, slide the coil out on the coil channel
sup-
ports and rotate
the complete coil 180 degrees.
Remove
the
factory
installed
baffle
assembly
from
the
apex
of the
coil by using
a 5/16"
nutdriver
to
remove
the
screws.
For
the
TEE3C40-65
units, there
is a coil support
tab at
the top of the coil connected
to the case must be
removed
first. Replace this baffle with the factory
supplied
narrow
coil baffle using the screws
re-
moved previously.
See Figure
11.
When instalfing
the narrow
coil baffle,
make
sure to
align the baffle up with the holes so NOT to puncture
the coil tubing.
d.
J
Figure 9
The coil is then inserted
back into the cabinet
on
the coil channels
located
near
the center
of the
unit.
Do not reattach
coil support
tab.
Also to-
tate the coil access panel 180 degrees and install.
The unit is now horizontal
left with front access.
e. If the unit is suspended,
it must
be supported
from the bottom
near
both ends as well as the
middle
to prevent
sagging.
The service
access
must
remain
unobstructed.
If the unit
is sup-
ported
along
the length
of the front
and back
with rails, the air handler
only needs to be sus-
pended at both ends. See Figure
8.
f. If the unit is not suspended
it must be supported
as mentioned
above and isolated carefully
to
prevent
sound transmission.
Vibration
isolators
(purchased
locally) must be placed under the
unit.
g. It is always recommended
that an auxiliary
drain
pan be installed
under
a horizontal
air handler
(See Condensate
Piping) to prevent
possible dam-
age to ceilings.
h. Isolate
the auxiliary
drain
pan from the unit or
from the structure.
i.
Connect
the auxiliary
drain
line to a separate
drain line (no trap is needed in this line) and ter-
minate
according
to national
and local codes.
6
18-GEl 1D1-4