4.1.4 TYPICAL THROUGH THE WALL

If possible, design the installation so that the connector does not pass through a combustible wall. If during
your installation you must pass through a combustible wall, check with your building inspector before you
begin. Also check with the chimney connector manufacturer for any specifi c requirements.
Consult with your dealer regarding special connection components available for use for wall pass-throughs.
Use only parts that have been tested and listed for use in a wall pass-through.
SECTION
LISTED
CHIMNEY PIPE
TO
STOVE
THIMBLE
COMBUSTIBLE
OUTSIDE WALL
LISTED
CHIMNEY
2" (50.8mm)
CLEARANCE
INSULATED
"T"
WALL
SUPPORT
WALL SPACER
FOR OUTSIDE
WALL
MAINTAIN 2"
ROOF
(50.8mm) CLEARANCE
THROUGH EAVE
COMBUSTIBLE
CEILING
CHIMNEY
CONNECTOR
FLOOR
PROTECTOR
17
TERMINAL
STORM
COLLAR
FLASHING
COMBUSTIBLE
WALL