9 Attachment

Main Circuit Wire Gauges and Tightening Torques (for CE Standards)

Three-Phase 200 V Class

Model
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2018
-, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2025
-, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2033
-, +1, +2
B1, B2
266
Recomm.
Applicable
Gauge
Gauge
mm
2
mm
2
4
2.5 - 6
2.5
2.5 - 4
6
4 - 10
2.5
2.5 - 4
*2
*2
6
2.5 - 6
6
4 - 10
6
4 - 10
10
2.5 - 16
2.5
2.5 - 4
*2
6
6 - 16
10
2.5 - 16
10
2.5 - 16
16
4 - 25
4
2.5 - 6
10
6 - 16
YASKAWA TOMPYEULA5001C LA500 Installation and Operation Instructions
Wire
Terminal Screw
Stripping
Length
*1
Size
Shape
mm
10
M4
10
M4
10
M4
10
M4
-
M4
10
M4
10
M4
10
M4
10
M4
-
M5
10
M4
10
M4
18
M5
10
M4
-
M5
Tightening
Torque
N∙m (in∙lb)
1.5 - 1.7
(13.5 - 15)
1.5 - 1.7
(13.5 - 15)
1.5 - 1.7
(13.5 - 15)
1.5 - 1.7
(13.5 - 15)
1.2 - 1.5
(10.6 - 13.3)
1.5 - 1.7
(13.5 - 15)
1.5 - 1.7
(13.5 - 15)
1.5 - 1.7
(13.5 - 15)
1.5 - 1.7
(13.5 - 15)
2.0 - 2.5
(17.7 - 22.1)
1.5 - 1.7
(13.5 - 15)
1.5 - 1.7
(13.5 - 15)
2.3 - 2.5
(19.8 - 22)
1.5 - 1.7
(13.5 - 15)
2.0 - 2.5
(17.7 - 22.1)