Lennox EL195UHNE Installation Instructions Manual page 34

Hide thumbs Also See for EL195UHNE:
Table of Contents

Advertisement

Evaporator
(Trap at coil is optional)
Drain Pan
Piping from furnace and evaporator coil must slope down a minimum 1/4" per ft. toward trap
Furnace with Evaporator
Coil Using a Common Drain
(Trap at coil is optional)
(1" min. to 2" Max.above
condensatedrain connection)
Condensate
Drain Connection
FIGURE 54
Evaporator
(Trap at coil is optional)
Drain Pan
Furnace with Evaporator Coil Using a Separate Drain
(Unit shown in horizontal left-hand discharge position)
Coil
Condensate
Drain Connection
FIGURE 53
Evaporator drain
line required
Furnace with Evaporator Coil Using a Common Drain
(Unit shown in horizontal left−hand discharge position)
Coil
Condensat e Drai n
Connection
Piping from furnace and evaporator coil must slope
down a minimum 1/4" per ft. toward trap
FIGURE 55
4"min
5"max
5' max.
PVC Pipe Only
When combining the furnace and evaporator coil
drains together, the A/C condensate drain outlet must
be vented to relieve pressure in order for the furnace
pressure switch to operate properly.
4"min
5"max
5' max.
PVC Pipe Only
Page 34
Field Provided Vent
(4" min. to 5" max. above
condensate connection)
.
IMPORTANT
(4" min. to 5" Max.above
condensatedrain connection)