Lennox EL195UHNE Installation Instructions Manual page 20

Hide thumbs Also See for EL195UHNE:
Table of Contents

Advertisement

NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake
and Exhaust must be same pipe size.
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent
length calculation.
Number Of
90° Elbows
040
1
81
2
76
3
71
4
66
5
61
6
56
7
51
8
46
9
41
10
36
Number Of
90° Elbows
040
1
73
2
68
3
63
4
58
5
53
6
48
7
43
8
38
9
33
10
28
TABLE 5 Continued
Standard Termination at Elevation 4501 - 7500 ft
2" Pipe
Model
060
080
41
34
36
29
31
24
26
19
21
14
16
9
11
n/a
n/a
Concentric Termination at Elevation 4501 - 7500 ft
2" Pipe
Model
060
080
33
32
28
27
23
22
18
17
13
12
n/a
n/a
100
040
138
133
128
123
118
n/a
113
108
103
98
93
100
040
121
116
111
106
101
n/a
96
91
86
81
76
Page 20
3" Pipe
Model
060
080
105
100
100
95
95
90
90
85
85
80
80
75
75
70
70
65
65
60
60
55
3" Pipe
Model
060
080
89
89
84
84
79
79
74
74
69
69
64
64
59
59
54
54
49
49
44
44
100
65
60
55
50
45
40
35
30
25
20
100
61
56
51
46
41
36
31
26
21
16