1.5.2 Installation of wired remote controller

(a) Selection of installation location
Avoid the following locations
1) Direct sunlight.
2) Close to heating device.
3) Highly humid or water splashing area.
4) Uneven surface.
(b) Installation procedure
a) Exposed fiting
1) Open the remote controller cover and unscrew
the screw located beneath the switch.
2) Open the remote controller case.
• Put a screw driver (flat-head) into the concav-
ity made on the upper part of a remote control-
ler and twist it lightly to open the casing.
3) The cord of a remote controller can only be
pulled out in the upward direction.
• Cut off with nippers or a knife a thin walled
part made on the upper end of the rmote con-
troller bottom casing, and then remove burrs
with a file or the like.
4) Fix the remote controller bottom casing onto
a wall with two wood screws supplied as ac-
cessories.
5) Connect the remote controller to the termi-
nal block. Connect the terminals of the re-
mote controller to the indoor unit with the
same numbers. Because the terminal block
has polarity, the device becomes inoperative
if there are wrong connections.
Terminals: xRed wire, YWhite wire, ZBlack wire
• Use a cord of 0.3mm
2
0.5mm
(maximum) for a remote controller
cord. Remove a sheathe of the remote control-
ler cord for the section laid within the remote
controller casing.
Screw
Thin walled part
Upper
Lower case
Lower
Upper
Lower case
Lower
Upper
Upper case
Board
Red White Black
X Y Z
Lower
Wiring
2
(recommended) -
The length of each wire that should be left af-
ter a sheath is removed is as follows:
Black: 195mm, White: 205mm, Red: 125mm
6) Replace the top casing as before.
7) Use a cord clamp to attach the remote con-
8) Set the functions according to the types of
(b) Recessed fitting
1) The Electrical box and remote controller (shield
wire must be use in case of extension) are first
embedded.
Remote
controller cord
Cable outlet
2) Remote the upper case to the remote controller.
3) Attach the lower case to the Electricl box with
two M4 screws. (Head diameter must be 8 mm).
Choose either of the following two positions in
fixing it with screws.
4) Connect the remote controller cord to the remote
controller.
Refer to [Exposed fitting].
5) Installation work is completed by replacing the
top casing onto the bottom casing as before.
6) Set the function switch according to the type of
the indoor unit. (Refer to 148 page)
Precation in Extending the Remote controller cord
Maximum total extension 600m.
The cord should be a shielded wire.
● For all types : 0.3mm
Note (1) Use cables up to 0.5mm
● The shielded wire should be grounded at one side only.
Indoor unit
(This side is not grounded)
136
-
-
ength of the
section where a
sheath is removed
troller cord to the wall.
indoor unit. See Section "Function Setting''.
Electrical box
Not included
Cable outlet
Upper
Cut off with a knife or the like thin walled parts
intended for screw holes, and then fix it with
screws.
Lower
wo M4 screws
(Head diameter must be 8mm)
(not included)
× 3 cores
2
2
(maximum) for those laid inside
the remote controller unit casing and connect to a different
size cable at a vicinity point outside the remote controller
unit, if necessary.
100.Within 100-200m............0.55 mm
Within 300m............0.75 mm
Within 400m............1.25 mm
Within 600m............2.05 mm
Earth wiring
Remote controller cord
(Shielded wire)
Remote controller
switch
Upper
Lower case
Lower
× 3 cores
2
× 3 cores
2
× 3 cores
2
× 3 cores
2

Hide quick links: