Ol Signal Output Timer (Pr. 157) - Mitsubishi Electric FR-A520-0.4K Instruction Manual

Hide thumbs Also See for FR-A520-0.4K:
Table of Contents

Advertisement

4.2.48 OL signal output timer (Pr. 157)

Pr. 157 "OL signal waiting time"
Use this parameter to set whether the overload alarm signal (OL signal) is output immediately or a preset
period of time after occurrence of an overload status.
Parameter
Factory Setting
Number
157
0
<Setting>
Refer to the following table and set the parameter:
Pr. 157 Setting
0
Output immediately.
0.1 to 25
Output after the set time (s) has elapsed.
9999
Overload alarm signal is not output.
Pr. 158
Refer to Pr. 54.
Setting Range
0 to 25 s, 9999
9999: No signal output
Overload status (OL output)
L output signal
Description
157
Get other manuals https://www.bkmanuals.com
R elated param eters
Pr. 190 to Pr. 195
"output terminal function selection"
Remarks
Set time (s)
PARAMETERS
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents