3) Harmonic suppression technique requirement
If the outgoing harmonic current is higher than the maximum value per 1kW (contract power) × contract
power, a harmonic suppression technique is required.
4) Harmonic suppression techniques
No.
Item
Reactor installation
1
(ACL, DCL)
High power factor
2
converter
(FR-HC)
Installation of power
3
factor improving
capacitor
Transformer multi-
4
phase operation
5
AC filter
6
Active filter
Install a reactor (ACL) in the AC side of the inverter or a reactor (DCL) in its DC side or both to
suppress outgoing harmonic currents.
The converter circuit is switched on-off to convert an input current waveform into a sine wave,
suppressing harmonic currents substantially. The high power factor converter (FR-HC) is used
with the standard accessory.
When used with a series reactor, the power factor improving capacitor has an effect of absorbing
harmonic currents.
Use two transformers with a phase angle difference of 30° as in
an effect corresponding to 12 pulses, reducing low-degree harmonic currents.
A capacitor and a reactor are used together to reduce impedance at specific frequencies,
producing a great effect of absorbing harmonic currents.
This filter detects the current of a circuit generating a harmonic current and generates a harmonic
current equivalent to a difference between that current and a fundamental wave current to
suppress a harmonic current at a detection point, providing a great effect of absorbing harmonic
currents.
37
Get other manuals https://www.bkmanuals.com
INSTALLATION AND WIRING
Description
-∆, ∆-∆ combination to provide
2