Performance And Electrical Data - Trane A4AH6E19A1B30B Installation Manual

Convertible air handlers
Table of Contents

Advertisement

Performance and Electrical Data

Table 4. Air Flow Performance
EXTERNAL STATIC
(in w.g)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
1.
Values are with wet coil, no filter, and no heaters
2.
CFM Correction for dry coil = Add 3%
3.
† = Factory Setting
4.
Low = Taps 1–2, Med = Tap 3, Med-High= Tap 4, High = Tap 5
Table 5. Electrical Data
No. of
Heater Model No.
Circuits/
Phases
No Heater
BAYHTR1504BRK
1/1
BAYHTR1504LUG
BAYHTR1505BRK
1/1
BAYHTR1505LUG
BAYHTR1508BRK
1/1
BAYHTR1508LUG
BAYHTR1510BRK
1/1
BAYHTR1510LUG
BAYHTR3510LUG
1/3
* = Motor Amps
18-GF14D1-1C-EN
A4AH6E19A1B30B
High
Med-High
860
817
767
709
644
571
491
A4AH6E19A1B30B
240 Volt
Capacity
Minimum
Heater
Circuit
Amps per
Ampacity
kW
BTUH
Circuit
4.1 *
3.8
13100
16.0
4.8
16400
20.0
7.7
26200
32.0
9.6
32800
40.0
9.6
32800
23.1
AIRFLOW
Speed Taps — 208 – 230 VOLTS
Med †
773
652
732
589
679
515
612
431
533
336
441
232
336
116
Capacity
Maximum
Overload
Protection
kW
8
15
28
30
2.9
33
35
3.6
12300
48
50
5.8
19700
58
60
7.2
24600
36
40
7.2
24600
Low
589
528
445
339
210
208 Volt
Minimum
Heater
Circuit
Amps per
Ampacity
BTUH
Circuit
4.1 *
8
9800
13.8
25
17.3
29
27.7
42
34.6
51
20.0
32
Maximum
Overload
Protection
15
25
30
45
60
35
15