Download Print this page

Carrier 48VL-E Installation Instructions Manual page 15

Comfort 14 seer single-packaged air conditioner and gas furnace system with puron (r-410a) refrigerant

Advertisement

48VL-(E, F): Installation Instructions
4. Divide number of seconds in Step 3 into 3600 (number of seconds
in one hr).
5. Multiply result of Step 4 by the number of cubic feet (cu ft) shown
for one revolution of test dial to obtain cubic feet (cu ft) of gas flow
per hour.
6. Multiply result of Step 5 by Btu heating value of gas to obtain total
measured input in Btuh. Compare this value with heating input
shown in
Table 5
(Consult the local gas supplier if the heating value
of gas is not known).
EXAMPLE: Assume that the size of test dial is 1 cu ft, one revolution
takes 32 sec, and the heating value of the gas is 1050 Btu/ft3. Proceed as
follows:
1. 41 sec. to complete one revolution
2. 3600 / 41 = 87.8
3
3. 87.8 x 1 = 87.8 ft
of gas flow/hr
4. 87.8 x 1050 = 92,190 Btuh input
If the desired gas input is 89,000 Btuh, only a minor change in the
manifold pressure is required.
Observe manifold pressure and proceed as follows to adjust gas input:
Table 4 – High Altitude Compensation, Natural Gas - Single and Three Phase Models
Nameplate Input (Btu/hr)
60,000
89,000
*. In the U.S.A., the input rating for altitudes above 2000 ft (610m) must be reduced by 4% for each 1000 ft (305 m) above sea level.
In Canada, the input rating for altitudes from 2001 to 4500 ft (611 to 1372 m) above sea level must be derated by 10% by an authorized gas conversion station or dealer.
For Canadian Installations from 2000 to 4500 ft (610-1372 m), use U.S.A. column 2001 to 3000 ft (611 to 914 m).
†. Altitude of 2001 and above is not allowed.
Heating Input
Number of Orifices
(BTUH)
60,000
89,000
*. When a unit is converted to propane, different size orifices must be used. See separate, natural-to-propane conversion kit instructions.
†. Based on altitudes from sea level to 2000 ft (610 m) above sea level. In U.S.A. for altitudes above 2000 ft (610 m), reduce input rating 4 percent for each additional 1000 ft (305
m) above sea level. In Canada, from 2000 ft (610 m) above sea level to 4500 ft (1372 m) above sea level, derate the unit 10 percent.
N/A = Not applicable (Units are not convertible to propane)
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Table 5 – Heating Inputs
Gas Supply Pressure (IN. W.C.)
Natural
Min
1
4.0
1
4.5
1. Remove regulator cover screw over plastic adjustment screw on gas
valve (See
Fig.
2. Turn plastic adjustment screw clockwise to increase gas input, or
turn plastic adjustment screw counterclockwise to decrease input
(See
Fig.
13). Manifold pressure must be between 3.2 and 3.8 IN.
WC.
FIRE AND UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death
and/or property damage.
Unsafe operation of the unit may result if manifold pressure is outside
this range.
3. Replace regulator cover screw on gas valve (See
4. Turn off gas supply to unit. Remove manometer hose and barbed
pressure tap. Replace pressure tap cover using an allen wrench (See
Fig.
13.) Turn on gas to unit and check for leaks.
Rated Heating Input (Btu/hr), Natural Gas at Installation Altitude Above Sea
Propane
Max
Min
13.0
N/A
13.0
N/A
15
13).
WARNING
!
*
Level, U.S.A.
0 to 2000 ft
(0-610 m)
60,000
89,000
Manifold Pressure (IN. W.C.)
*†
Max
Natural
N/A
3.2~3.8
N/A
3.2~3.8
Fig.
13).
*†
Propane
N/A
N/A

Advertisement

loading

This manual is also suitable for:

48vl-f