Trane Mitsubishi Electric CITY MULTI Series Technical & Service Manual page 26

Table of Contents

Advertisement

8-2. DRY OPERATION
RETURN SELECT
MENU
HOLD
.
Control Mode
1. Temperature
1-1. Determining temperature adjustment function
adjustment
(Function to prevent restarting for 3 minutes)
function
Setting the Dry thermo by the thermostat signal and the room temperature (TH21).
Dry thermo-ON Room temperature ] Set temperature + 2°F
Dry thermo-OFF Room temperature [ Set temperature
Room temperature
Over 64°F
Below 64°F
1-2. Anti-freeze control
No control function
2. Fan
Indoor fan operation control depends on the compressor conditions.
Note: Fan speed change is not allowed during DRY operation.
3. Drain pump
Operates as it would in COOL operation.
4. Vane
Settings are the same in DRY operation as they are in COOL operation.
(up/down vane
position change)
OCHT746A
ON
OFF
Control Details
3 minutes passed since
starting operation
Thermostat signal Room temperature (T1)
ON
OFF
Dry thermo
ON
Excluding the following
OFF
Room temp. < 64°F
<How to operate>
1 Press ON/OFF button.
2 Press [F1] button to display DRY.
3 Press [F2] [F3] button to set the set temperature.
<How to operate>
1 Press POWER ON/OFF button.
2 Press the operation MODE button to display DRY.
3 Press the TEMP. button to set the set temperature.
NOTE: The set temperature changes 1°F when the
button is pressed one time. Dry 67 to 87°F
Dry thermo-
ON time
(min)
T1 ] 83°F
9
83°F > T1 ] 79°F
7
79°F > T1 ] 75°F
5
75°F > T1
3
Unconditional
3
Dry thermo OFF
Fan speed notch
[Low]
26
Remarks
Dry thermo-
OFF time
(min)
3
3
3
3
10
Stop
[Low]
or

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents