3-4. ELECTRICAL PARTS SPECIFICATIONS
Model name
Symbol
Parts name
Room temperature
TH21 Resistance 30°F/15.8 kΩ, 50°F/9.6 kΩ, 70°F/6.0 kΩ, 80°F/4.8 kΩ, 90°F/3.9 kΩ, 100°F/3.2 kΩ
detection thermistor
Pipe temperature
TH22 Resistance 30°F/15.8 kΩ, 50°F/9.6 kΩ, 70°F/6.0 kΩ, 80°F/4.8 kΩ, 90°F/3.9 kΩ, 100°F/3.2 kΩ
dection thermistor/liquid
Pipe temperature
TH23 Resistance 30°F/15.8 kΩ, 50°F/9.6 kΩ, 70°F/6.0 kΩ, 80°F/4.8 kΩ, 90°F/3.9 kΩ, 100°F/3.2 kΩ
detection thermistor/gas
Fuse
FUSE
(Indoor controller board)
Fan motor
Vane motor
Drain pump
Drain float switch
Linear expansion valve
Power supply terminal
block
Transmission terminal
block
MA remote controller
TB15
terminal block
OCHT746A
TPLFYP006EM140B
TPLFYP008EM140B
TPLFYP012EM140B
TPLFYP015EM140B
MF
8-pole OUTPUT 50 W
MV
DP
FS
12 VDC Stepping motor drive port dimension ø3.2
LEV
TB2
TB5
TPLFYP018EM141B
TPLFYP024EM140B
UL 6.3 A 250 VAC
MSBPC20M04
12 VDC, 300 Ω/phase
PMD-12D13ME-5
INPUT 3.9 W 36 ℓ/Hr
Open/short detection
(0–2000pulse)
EDM-40YGME
(L1, L2, GR) 330 V, 30 A
(M1, M2, S) 250 V, 20 A
(1, 2) 250 V, 10 A
17
TPLFYP030EM140B
TPLFYP036EM140B
TPLFYP048EM140B
8-pole OUTPUT, 120 W
12 VDC Stepping motor drive
port dimension
ø5.2 (0–2000pulse)
EDM-80YGME

Hide quick links: