5
Commissioning with web server
The following engineering tools can be used for commissioning and configuring the converter:
•
Web server
–
Integrated in the converter
–
Suitable for online diagnostics and configuration without a control system
•
Startdrive
–
If the converter is completely configured in the TIA Portal
–
If the converter is configured together with a control system (e.g. SIMATIC PLC)
The following description refers exclusively to commissioning via the web server.
For more information about commissioning with Startdrive, see the Operating Instructions
(https://support.industry.siemens.com/cs/ww/en/ps/29596).
5.1
Supported hardware and software
Use the web server integrated in the converter for commissioning. The following operating units and browsers are supported
by the web server:
Operating units
•
PC
•
Smartphone or tablet PC
Mobile devices can be connected to the converter via
third-party Ethernet OTG adapters or external WLAN
access points.
Siemens recommends that you use the latest version of the browsers.
1)
5.2
Preparing for commissioning
Proceed as follows to prepare for commissioning:
1. Mount the motor on the mechanical system. Connect the motor to the converter.
2. Connect the converter to the operating unit via the service interface (X127).
3. Switch the converter on.
4. Start the Internet browser for commissioning.
5. Enter the IP address of the converter.
–
Preset IP address: 169.254.11.22
–
Preset subnet mask: 255.255.0.0
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
A5E52388930A AA, 07/2023
Browsers and versions
1)
•
Apple Safari (≥ Version 15.0)
•
Google Chrome (≥ Version 83)
•
Microsoft Edge (≥ Version 88)
•
Mozilla Firefox (≥ Version 91)
23