Lennox 4HP17L Installation Instructions Manual page 16

Single stage heat pump
Table of Contents

Advertisement

DS2
DS1
Type
Green
Red
OFF
OFF
Status
Simultaneous
Status
SLOW Flash
Alternating
Status
SLOW Flash
Simultaneous
Fault
FAST Flash
Alternating
Fault
FAST Flash
ON
ON
Fault
SLOW
OFF
Fault
Flash
OFF
ON
Lockout
SLOW
OFF
Fault
Flash
ON
OFF
Lockout
(Each fault adds 1 strike to that code's counter; 5 strikes per code = LOCKOUT)
Page 16 of 21
DS1 and DS2 System Status, Fault and Lockout Codes
Condition / Code
No power (24V) to control
Power Problem
board terminals R and C or
control board failure.
Unit operating normally or in
Normal operation
standby mode.
5-minute anti-short
Initial power up, safety trip, end
cycle delay
of room thermostat demand.
Sensor being detected open or shorted or out of temperature range. Control
Ambient Sensor
board will revert to time/temperature defrost operation. (System will still heat or
Problem
cool).
Sensor being detected open or shorted or out of temperature range. Control
Coil Sensor
board will not perform demand or time/temperature defrost operation. (System
Problem
will still heat or cool.)
Demand Defrost
Indicates that demand defrost control has internal component failure. Cycle
Control Failure
24VAC power to control board. If code does not clear, replace control board.
Low Pressure Fault
• Restricted air flow over
indoor or outdoor coil.
• Improper refrigerant charge
Low Pressure
in system.
Lockout
• Improper metering device
installed or incorrect
High Pressure Fault
operation of metering device.
• Incorrect or improper sensor
location or connection to
High Pressure
system.
Lockout
Table 6. Control Board Diagnostic LEDs
Possible Cause(s)
Issue 2225
Solution
1. Check control transformer power (24V).
2. If power is available to control board and
LED(s) do not light, replace control board.
None required.
None required (jumper TEST pins to override)
• Remove any blockages or restrictions from
coils and/or fans. Check indoor and outdoor
fan motor for proper current draws.
• Check system charge using subcooling
method.
• Check system operating pressures and
compare to unit subcooling tables located on
unit access panel.
• Make sure all pressure switches and sensors
have secure connections to system to
prevent refrigerant leaks or errors in pressure
and temperature measurements.
508270-01