Carrier 30KAV-ZE Series Installation, Operation And Maintenance Instructions page 73

Liquid chiller with variable speed screw compressor and greenspeed smart technology
Table of Contents

Advertisement

12 - OPTIONS
High pressure dual pump motors (option 116W)
No.
Description
(2)
(3)
Nominal efficiency at full load and nominal voltage
1
Nominal efficiency at 75% of full load and nominal voltage
Nominal efficiency at 50% of full load and nominal voltage
2
Efficiency level
3
Year of manufacture
Manufacturer's name and trademark, commercial registration number
4
and place of manufacturer
5
Product's model number
6
Number of motor poles
7-1
Nominal shaft power output at full load and nominal voltage (400 V)
7-2
Maximum input power (400 V)
8
Nominal input frequency 
9-1
Nominal voltage
9-2
Maximum current drawn (400 V)
10
Nominal speed
11
Product disassembly, recycling or disposal at end of life
Operating conditions for which the motor is specifically designed
I - Altitudes above sea level
II - Ambient air temperature
12
III - Maximum operating temperature
IV - Potentially explosive atmospheres
(1)  Required by regulation No. 640/2009 concerning the application of directive 2009/125/EC on the eco-design requirements for electric motors.
(2)  Item number imposed by regulation No. 640/2009, annex I2b.
(3)  Description given by regulation No. 640/2009, annex I2b.
(4)  To obtain the maximum input power for a unit with hydraulic module, add the "maximum operating input power" for the unit (see Electrical data table) to the pump power.
(5)  To obtain the maximum unit operating current draw for a unit with hydraulic module add the "maximum unit operating current draw" (Electrical data table) to the pump 
current draw.
(6) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.
(4)
(5)
350A
400A
450A
%
90,3
91,3
91,3
%
90,3
91,4
91,4
%
88,9
90,3
90,3
-
This information varies depending on the manufacturer
-
and model at the time of incorporation. Please refer to
the motor nameplates.
-
Same as above
-
Same as above
-
2
2
kW
7,5
11
11
kW
8,31
12,05
12,05
Hz
50
50
50
V
A
13,20
18,70
18,70
r/s -
48,9
49,1
49,1
rpm
- 2935
- 2945
- 2945
Disassembly using standard tools. Disposal and
-
recycling using an appropriate company.
m
°C
Please refer to the operating conditions given
°C
in this manual or in the specific conditions in 
the Carrier selection programs.
-
Non-ATEX environment
500A
550A
600A
91,3
91,9
91,9
91,4
92,1
92,1
90,3
90,4
90,4
IE3
2
2
2
2
11
15
15
12,05
16,38
16,38
50
50
50
3 x 400
18,70
25,20
25,20
49,1
49,1
49,1
- 2945
- 2945
- 2945
< 1000
(6)
< 40
73

Advertisement

Table of Contents
loading