Maintenance Position - Riello 40 G20D Installation, Use And Maintenance Instructions

Kerosene and gas oil burner, two stage operation
Table of Contents

Advertisement

Fuel tank
If water or contamination is present within the fuel tank, it is es-
sential that this is removed before the equipment is to be used.
This is extremely important when gas oil containing Bio diesel is
in use. If in doubt about how to achieve this then please contact
the fuel or oil tank supplier.
Boiler
Clean the boiler as indicated in its accompanying instructions in
order to maintain all the original combustion characteristics in-
tact, especially the flue gas temperature and combustion cham-
ber pressure.
8.3

Maintenance position

Access to the combustion head, diffuser disc / electrodes
unit and nozzle (Fig. 29)
 Remove the burner out of the boiler, after loosing the fixing
nut to the flange.
 Hook the burner to the flange 1), by removing the combus-
tion head 2) after loosing the fixing screws 3).
 Remove the diffuser disc-holder assembly 9) from the noz-
zle-holder 8) after loosing its fixing screw.
 Screw the nozzle 10).
2
3
4
6
5
Maintenance
Combustion
In case the combustion values found at the beginning of the inter-
vention do not respect the standards in force or, in any case, do
not correspond to a proper combustion, contact the Technical
Assistant and have him carry out the necessary adjustments.
Allow the burner to work for 10 min. and then check the combus-
tion readings with the parameters indicated within the appliance
instruction manual. Then carry out a combustion check verify-
ing:
– Smoke temperature at the chimney;
– Content of CO
– Content of CO (ppm)
– Smoke value according to opacity smokes index according to
8.3.1
The safety components must be replaced at the end of their life
cycle indicated in Tab. F. The specified life cycles do not refer to
the warranty terms indicated in the delivery or payment
conditions.
Safety component
Flame control
1
Flame sensor
Gas valves (solenoid)
Pressure switches
Pressure adjuster
Servomotor (electronic
cam) (if present)
Oil valve (solenoid) (if
present)
D8056
Oil regulator (if present)
Oil pipes/ couplings
(metallic) (if present)
Fan impeller
D8057
Fig. 29
23
GB
(%)
2
Bacharach scale
Safety components
Life cycle
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
15 years
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years
10 years or 500,000 start-ups
Tab. F
2903397