Mains
Green LED indicates that it is
contactor
possible to close the Mains
Contactor (only in AMF mode), if
the Generator contactor is open.
Alarm
Flashing red LED indicates that an
alarm is present. A continuous red
LED indicates that the alarm has
been acknowledged by the user. The
exact alarm is shown on the display.
Qc2002™ Menu Overview
At Qc2002™, the LCD will show following
information:
– in
Normal condition (scroll through the
information using UP and DOWN):
Status (eg: preheat, crank, cooldown, extended
stop time, ...) (pop-up: this display is only
shown when a Special status comes up)
Line voltages of the generator
Controller type & version
Parameter list
Alarm list
LOG list
Service Timer 1 & Service Timer 2
Battery Voltage
RPM (speed)
Coolant temperature
Oil pressure
Fuel level
kWh counter
Power factor, the frequency of the generator
and the frequency of the mains
Line voltage, frequency and active power of
the generator
Active, reactive and apparent power of the
generator
Generator currents
Phase voltages of the mains
Line voltages of the mains
Phase voltages of the generator
- 27 -
– in
Alarm
condition
(scroll
information using UP and DOWN):
a list of all active Alarms
It's possible to scroll through the views, using the UP
and DOWN buttons. The scrolling is continuous.
If a Special status comes up, the Status Display is
shown.
If an Alarm comes up, the Alarm Display is shown.
Line voltages generator display
G L1-L2
G L2-L3
G L3-L1
This view shows the line voltages of the generator.
Controller type and version display
Qc2002
1.00.1
This view shows the controller type and the ASW
version number.
through
the
400V
400V
400V