Vitodens 200-W B2HA 112, 150, 399, 530 Service
Solar
(continued)
Coding in the factory setting
23:4
24:40
25:50
26:1
27:15
28:3
Stop temperature differential
for central heating
backup: 4 K.
(code 20:4 must be selected)
Start temperature for thermostat
function 104°F (40°C).
(code 20:5 or 20:6 must be
selected)
Stop temperature for thermostat
function 122°F (50°C).
(code 20:5 or 20:6 must be
selected)
Priority for DHW tank 1 with
alternate heating.
Only when setting code 20:8.
Alternate heating time 15 minutes.
The DHW tank without priority
is heated at most for the
duration of the set alternate
heating time if the DHW tank
with priority is heated up.
Alternate pause time 3 minutes
After the selected alternate
heating time for the DHW tank
without priority has expired, the
rise in collector temperature is
captured during the alternate
pause time.
Possible change
23:2
Stop temperature differential
to
for central heating backup is
23:30
adjustable from 1 to 29 K.
24:0
Start temperature for thermostat
to
function adjustable from 0 to 100 K.
24:100
25:0
Start temperature for thermostat
to
function is adjustable from
25:100
0 to 100 K.
26:0
Priority for DHW tank 1 without
alternate heating.
26:2
Priority for DHW tank 2 without
alternate heating.
26:3
Priority for DHW tank 2 with
alternate heating.
26:4
Alternate heating without priority
for one of the DHW tank.
27:5
The alternate heating time is
to
adjustable from 5 to 60 minutes.
27:60
28:1
The alternate pause time is
to
adjustable from 1 to 60 minutes.
28:60
Coding 2
61