Viessmann VITODENS 200-W B2HA 150 Service Instructions Manual page 78

Hide thumbs Also See for VITODENS 200-W B2HA 150:
Table of Contents

Advertisement

Troubleshooting
Fault Codes
(continued)
Fault code
Detailed fault
on display
code*2
EE
132
EF
138
F0
-
F1
135
F2
129
F3
139
F6
-
F8
148
F9
151
or
152
*1 Control mode: Boiler/burner fully operational (fault code must be verified and reset).
Burner in fault mode: Boiler control requires manual reset before burner can resume operation.
Burner blocked: If fault cause is corrected, burner resumes operation.
*2 Detailed fault code coding address 38:xx (if available).
78
System behavior*1
Burner in a fault mode
Burner in a fault mode
Burner blocked
Burner in a fault mode
Burner in fault mode
Burner in fault mode
Burner in a fault state
Burner in fault mode
Burner in fault mode
Vitodens 200-W B2HA 112, 150, 399, 530 Service
Cause
At burner start, flame
signal is missing or too
weak
Flame is lost immediately
after it has built (during
the safety time)
Internal fault
Maximum flue gas
temperature exceeded
230ºF (110ºC) limit.
Fixed high limit switch
open (activated)
Flame signal already
present at burner start
Boiler water
temperature sensor
temperature values
vary too widely from
one another
Gas valve closes too
late
Fan speed too low
during burner start
Corrective action
Check gas supply (gas pressure
and gas regulator). Check gas
train. Check ionization electrode
and connecting cable.
Check ignition:
- Connecting leads to ignition
module and ignition electrode.
- Ignition electrode gap and
contamination (see page 23).
Check condensate drain.
Press reset button R.
Check gas supply (gas pressure
and gas regulator). Check flue
gas/ventilation air system for
flue gas recirculation. Check
ionization electrode (replace
if required):
- Distance to burner gauze
assembly (see page 23).
- Contamination of electrode
Press reset button R.
Replace the control unit.
Check heating system fill level.
Bleed air from system. Check
circulation pump. Check boiler
water temperature sensor and
cable. Press reset button R after
vent system has cooled down.
Check heating system fill
level. Check the circulation
pump. Bleed air from the
system. Check fixed high limit
switch and connecting cables.
Press reset button R.
Check the ionization electrode
and connecting cable.
Press reset button R.
Replace boiler water
temperature sensors
Check the gas valve.
Check both control wiring/
connections.
Press reset button R.
Check the fan, the fan cables
and power supply. Check the
fan control.
Press reset button R.

Advertisement

Table of Contents
loading

Table of Contents