Viessmann VITODENS 200-W B2HA 150 Service Instructions Manual page 66

Hide thumbs Also See for VITODENS 200-W B2HA 150:
Table of Contents

Advertisement

Coding 2
Heating Circuit 1, 2 and 3
Coding in the factory setting
E5:0
E6:...
NOT USED
E7:50
NOT USED
E8:1
NOT USED
E9:45
NOT USED
F1:0
F2:8
F5:12
*1
Party mode ends automatically in the "Heating and DHW" program, when the system changes over to operation with
standard room temperature.
66
(continued)
Do not adjust
Maximum speed of the variable
speed heating circuit pump in
% of the maximum speed in
standard mode. Value is
specified by boiler-specific
parameters
Minimum speed of the variable
speed heating circuit pump:
30% of the maximum speed
Minimum speed in operation
with reduced room temperature
subject to the setting in coding
address "E9"
Speed of the variable speed
heating circuit pump: 45% of
the maximum speed during
operation with reduced room
temperature
Do not adjust
Time limit for party mode
or external heating program
changeover via pushbutton:
8 h
*1
Run-on time of the boiler circuit
pump in heating mode: 12
minutes.
Vitodens 200-W B2HA 112, 150, 399, 530 Service
Possible change
--
E6:0
Maximum speed adjustable
to
from 0 to 100%.
E6:100
E7:0
Minimum speed adjustable from
to
0 to 100% of the maximum
E7:100
speed.
E8:0
Speed subject to the setting in
coding address "E7".
E9:0
Speed adjustable from 0 to 100%
to
of the maximum speed during
E9:100
operation with reduced room
temperature.
--
F2:0
No time limit for party mode
F2:1
Time limit adjustable from 1 to
to
12 h
F2:12
F5:0
No run-on time for the circulation
pump in the heating circuit
connection set.
F5:1
Run-on time of the circulation pump
to
in the heating circuit connection set
F5:20
adjustable from 1 to 20 minutes.
--
--
*1.
*1.

Advertisement

Table of Contents
loading

Table of Contents