Toshiba MMW-UP0271LQ-E Service Manual page 60

Hide thumbs Also See for MMW-UP0271LQ-E:
Table of Contents

Advertisement

Check code
Main
Outdoor 7-segment display
remote
Check
Sub-code
controller
code
1∗: Compressor
1 side
2∗: Compressor
2 side
H01
H01
1∗: Compressor
1 side
2∗: Compressor
2 side
H02
H02
1∗: Compressor
1 side
2∗: Compressor
H03
H03
2 side
H05
H05
H06
H06
H07
H07
Location
Description
of
detection
Compressor
Compressor
P.C. board
breakdown
Compressor
Compressor
P.C. board
trouble (lockup)
MG-CTT trouble
Compressor
Current
P.C. board
detection
circuit trouble
I/F
TD1 sensor
miswiring
(incomplete
insertion)
I/F
Activation of
low-pressure
protection
I/F
Low oil level
protection
Indoor unit (including Hot Water Module)
Check code detection
System status
condition(s)
All stop
Inverter current detection
circuit detects overcurrent
and shuts system down.
All stop
Overcurrent is detected
several seconds after
startup of inverter
compressor.
All stop
Current flow of at least
specified magnitude is
detected despite inverter
compressor having been
shut turned off.
All stop
Discharge temperature of
compressor 1 (TD1) does
not increase despite
compressor being in
operation.
All stop
Low-pressure Ps sensor
detects operating pressure
lower than 0.02MPa.
All stop
Operating compressor
detects continuous state of
low oil level for about 2
hours.
– 60 –
Check items (locations)
• Check power supply
voltage. (AC380V ± 10%).
• Check for failure in
compressor.
• Check for possible cause
of abnormal overloading.
• Check for failure in outdoor
P.C. board (Compressor).
• Check for failure in
compressor.
• Check power supply
voltage. (AC380V ± 10%).
• Check compressor system
wiring, particularly for open
phase.
• Check connection of
connectors/terminals on
Compressor P.C. board.
• Check conductivity of case
heater.
(Check for refrigerant
problem inside
compressor.)
• Check for failure in outdoor
P.C. board (Compressor).
• Check outdoor MG-CTT.
• Check current detection
circuit wiring.
• Check failure in outdoor
P.C. board (Compressor).
• Check installation of TD1
sensor.
• Check connection of TD1
sensor connector and
wiring.
• Check resistance
characteristics of TD1
sensor.
• Check for failure in outdoor
P.C. board (I/F).
• Check service valves to
confirm full opening
(both gas and liquid sides).
• Check outdoor PMVs for
clogging (PMV1, 2, 3).
• Check for failure in SV4
circuits.
• Check for failure in low-
pressure Ps sensor.
• Check indoor filter for
clogging.
• Check valve opening
status of indoor PMV.
• Check refrigerant piping for
clogging.
• Check operation of outdoor
fan (during heating).
• Check for insufficiency in
refrigerant quantity.
<All outdoor units in
corresponding line to be
checked>
• Check connection and
installation of TK1 and TK2
sensors.
• Check resistance
characteristics of TK1 and
TK2 sensors.
• Check for gas or oil leak in
same line.
• Check for refrigerant
problem inside compressor
casing.
• Check SV3D, SV3F valves
for failure.
• Check oil return circuit of
oil separator for clogging.
• Check oil equalizing circuit
for clogging.