Toshiba MMW-UP0271LQ-E Service Manual page 25

Hide thumbs Also See for MMW-UP0271LQ-E:
Table of Contents

Advertisement

Function CODE No. (DN Code) table (includes all functions needed to perform applied control on site)
DN
Item
Central control address
03
Demand control
(CN73)
0b
10 Type
11 Indoor unit capacity
Line address
12
Indoor unit address
13
Group address
14
28 Automatic restart of
power failure
HA terminal (CN061)
select
2E
60 Timer setting
(wired remote controller)
E0 Destination
FC Communication
protocol *1
Central device control
1FB
state
Indoor Unit
1FC
terminating resistance
Notice code
180
number 01
181 Notice code
number 02
182 Notice code
number 03
183 Notice code
number 04
184 Notice code
number 05
185 Notice code
number 06
186 Notice code
number 07
187 Notice code
number 08
188 Notice code
number 09
189 Notice code
number 10
0001: No.1 unit
0001: No.1 unit
00Un: Unfixed (When using U series remote controller)
0099: Unfixed (Other than U series remote controller)
0000: Demand input
0002: Card input setup.3
0004: Card input setup.4
0005: Fire alarm input
(Normal close)
0007: Card input setup.5
0009: Card input setup.2
0060: Hot Water Module
* refer to Type DN code [10]
0000: Unfixed
* Refer to Indoor Unit Capacity DN code [11]
0001: No.1 unit
0001: No.1 unit
00Un: Unfixed (When using U series remote controller)
0099: Unfixed (Other than U series remote controller)
0001: No.1 unit
0001: No.1 unit
00Un: Unfixed (When using U series remote controller)
0099: Unfixed (Other than U series remote controller)
0000: Individual
0002: Follower unit of group
00Un: Unfixed (When using U series remote controller)
0099: Unfixed (Other than U series remote controller)
0000: None
0000: Usual
0002: Fire alarm input
(Normal open)
0004: Notice code (201)
0000: Available
(can be performed)
0000: Japan
0004: Global
0000: TCC-LINK
0000: No central device control (Remote controller use is possible)
0001: Central device control (Remote controller use is impossible)
0000: OFF
0000: None
0001 ~ 0255 : Notice code
0129 : Notice code (201)
0130 : Notice code (202)
(0001 ~ 0255 : TU2C-LINK only)
(Refer to outdoor service manual)
Description
to
0064: No.64 unit ... TCC-LINK
to
0128: No.128 unit ... TU2C-LINK
0001: O2 sensor input
0002: Card input setup.3
(Normal open)
0006: Notice code (202)
0008: Card input setup.1
0001 to 0044
to
0064: No.30 unit ... TCC-LINK
to
0128: No.128 unit ... TU2C-LINK
to
0064: No.64 unit ... TCC-LINK
to
0128: No.128 unit ... TU2C-LINK
0001: Header unit of group
0001: Restart
0001: Card input setup.1 (3)
0003: Card input setup.2 (4)
0005: Card input setup.5
0001: Unavailable
(cannot be performed)
0003: TU2C-LINK
0001: ON
– 25 –
At shipment
00Un/0099:
Unfixed
0000: Demand
input
Depending on
model type
Depending on
model type
00Un/0099:
Unfixed
00Un/0099:
Unfixed
00Un/0099:
Unfixed
0000: None
0000: Usual
(HA terminal)
0000: Available
0004: Global
0000: TCC-LINK
0000: No central
device
control
0000: OFF
0000: None
0000: None
0000: None
0000: None
0000: None
0000: None
0000: None
0000: None
0000: None
0000: None