GEM 4241 Operating Instructions Manual page 15

Combi switchbox
Hide thumbs Also See for 4241:
Table of Contents

Advertisement

10.6 Assembling and installing the combi switchbox
Danger of explosion
▶ Risk of death or severe injury.
Do not use the product as a step or
foothold.
Prior to commissioning, ensure that
the cover is fully closed and that the
housing and the O-ring are not dam-
aged.
1. Move the actuator into the OPEN position.
2. Place the product as far as it will go into the actuator
opening, insert adapter 3 (see chapter 9.3) or stroke lim-
iter 1 (see chapter 9.4) and screw in clockwise against the
initial spring tension.
3. Use the spanner flat of the travel sensor to tighten the
product.
4. Turn the housing clockwise to align the pneumatic or elec-
trical connections.
5. Set the switch on the product.
Incorrect installation of the product.
▶ Damage to the housing.
Only tighten the product using the spanner flats provided
for this purpose.
www.gemu-group.com
DANGER
CAUTION
10.7 Setting the switching positions
1
1. Press clamping
tie bar 1 in with a
screwdriver.
3
4
Setting the upper switching
position:
4. Move the valve to the
OPEN position.
5. Squeeze and hold red
levers 3.
6. Push switch 4 on the
toothed bar into the de-
sired position.
7. Release red levers 3.
ð Switch 4 engages.
ð The upper switching
position is set.
12. Make the electrical connection (see "Electrical connec-
tion", page 17).
15 / 22
10 Assembly and installation
2. Turn the cover
3. Remove cover 2.
anticlockwise to
open the bay-
onet fitting.
5
6
Setting the lower switching
position:
8. Move the valve to the
CLOSED position.
9. Squeeze and hold red
levers 5.
10. Push switch 6 on the
toothed bar into the de-
sired position.
11. Release red levers 5.
ð Switch 6 engages.
ð The lower switching po-
sition is set.
2
GEMÜ 4241

Advertisement

Table of Contents
loading

Table of Contents