Page 1
WARNING: RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION AIR COOLED WARNING CONDENSING UNITS THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED INSTALLATION INSTRUCTIONS SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT, AND OPERATION OF THIS FO13C, FO14C & FO16C MODEL SERIES – UNIT.
IMPORTANT SAFETY INFORMATION WARNINGS: CAUTIONS: • These instructions are intended as an aid to • R-410A systems operate at approximately 60% higher pressures (1.6 times) than R-22 systems. Do qualified, licensed service personnel for proper not use R-22 service equipment or components on installation, adjustment, and operation of this R-410A equipment.
GENERAL INFORMATION Application WARNING: Before specifying any air conditioning equipment, Improper installation, or installation not a survey of the structure and a heat gain made in accordance with these instructions, calculation must be made. A cooling heat gain can result in unsatisfactory operation and/ calculation determines the amount of heat needed or dangerous conditions and can cause the to be removed.
GENERAL INFORMATION Electrical and Physical Data 13 SEER R-410A Single Stage Air Conditioner ELECTRICAL PHYSICAL Compressor Outdoor Coil Weight Minimum Fuse or HACR Rated Load Locked Rotor Circuit Rows [L/s] Lbs. Circuit Breaker Amperes Amperes Fan Motor Full Load Ampacity (FLA) [kg] Refrig.
GENERAL INFORMATION Electrical and Physical Data - cont. 14 SEER R-410A Single Stage Air Conditioner - Design Series "W" Southwest Regional ELECTRICAL PHYSICAL Compressor Fuse or HACR Outdoor Coil Weight Refrig. Motor Rated Load Locked Rotor Full Minimum Circuit Circuit Breaker Amperes Amperes Load...
INSTALLATION Choosing a Location Corrosive Environment IMPORTANT: Consult local and national building codes and ordinances for special The metal parts of this unit may be subject to installation requirements. Following location rust or deterioration if exposed to a corrosive environment. This oxidation could shorten the information will provide longer life and simplified servicing of the outdoor unit.
INSTALLATION Choosing a Location (cont.) • If installing a unit on a flat roof, use 4" x 4" For Units With Space [10.2 cm x 10.2 cm] or equivalent stringers Limitations positioned to distribute unit weight evenly and In the event that a space limitation exists, we will prevent noise and vibration.
INSTALLATION Tools and Refrigerant Tools Required for Installing Pressure: The pressure of R-410A is approximately 60% (1.6 times) greater than and Servicing R-410A Models R-22. Recovery and recycle equipment, pumps, Manifold Sets: hoses, and the like must have design pressure ratings appropriate for R-410A.
INSTALLATION Replacement Units To prevent failure of a new unit, the existing line set IMPORTANT: When replacing an must be correctly sized and cleaned or replaced. R-22 unit with an R-410A unit, either replace Care must be exercised that the expansion device the line set or ensure that residual mineral oil is is not plugged.
INSTALLATION Interconnecting Tubing (cont.) tubing length, fi ttings, vertical separation, acces- Interconnecting Tubing and sories, and fi lter dryers. The table below references Fitting Losses diff erent commonly used equivalent lengths. Refrigerant tubing is measured in terms of actual length and equivalent length. Actual length is used for refrigerant charge applications.
INSTALLATION Interconnecting Tubing (cont.) Example: A 3-Ton condensing unit is installed 50’ below the ID unit, requires a 75’ of 1/2” diameter liquid line, and 4 90° LR elbows. • Fitting Equivalent Length (ft.) = 4 x .9 = 3.6’ •...
INSTALLATION Interconnecting Tubing (cont.) and performance of the system. The procedure for Major Series selecting the proper suction line is as follows: Name Plate Factory Oil Charge Installed • The total amount of suction line needed Model # Compressor (oz) Capacity Voltage/Hz Phase...
INSTALLATION Interconnecting Tubing (cont.) For applications that are considered to have a long • Insulated liquid and suction line in unconditioned line set with the outdoor unit and indoor unit on the space only. same level the following is required: •...
Page 16
INSTALLATION Interconnecting Tubing (cont.) OUTDOOR UNIT ABOVE INDOOR SECTION LINE SET INSULATE LIQUID AND SUCTION LINE REFERENCE TABLE 2 FOR ELEVATION LIMITATIONS VERIFY SUB-COOLING PRIOR TO THROTTLING DEVICE TXV OR EEV AT INDOOR EVAPORATOR For applications that are considered to have a long •...
INSTALLATION Interconnecting Tubing (cont.) lineset. Commercially available flush kits are Tubing Installation not recommended due to the risk of residual Observe the following when installing correctly flushing agent being incompatible with POE oils sized type “L” refrigerant tubing between the or internal components.
INSTALLATION Interconnecting Tubing (cont.) • If tubing is to be run underground, it must be run in a sealed watertight chase. • Use care in routing tubing and do not kink or twist. Use a good tubing bender on the vapor line to prevent kinking.
INSTALLATION Interconnecting Tubing (cont.) Leak Testing Indoor coils have only a holding charge of dry nitrogen. Keep all tube ends sealed until connections are to be made. WARNING: Do not use oxygen to purge lines or pressurize system for leak test. Oxygen reacts violently with oil, which can cause an explosion resulting in severe personal injury or death.
WIRING Control Wiring WARNING: Turn off electric power CONTROL WIRING FOR GAS OR OIL FURNACE at the fuse box or service panel before making TYPICAL THERMOSTAT any electrical connections. Also, the ground SUBBASE FOR TYPICAL GAS OR OIL HEAT connection must be completed before making line voltage connections.
WIRING Control Wiring (cont.) Field wiring must comply with the National Electric Connect power wiring to line-voltage lugs located Code (C.E.C. in Canada) and any applicable local in the outdoor unit electrical box. (See wiring code. diagram attached to unit access panel.) Check all electrical connections, including Power Wiring factory wiring within the unit and make sure all...
START-UP Start-Up Even though the unit is factory-charged with Refrigerant-410A, the charge must be checked to the charge table attached to the service panel and adjusted, if required. Allow a minimum of 15 minutes of run time before analyzing charge. CAUTION: Single-pole contactors are used on all standard single-phase units...
START-UP Evacuation and Leak Testing Evacuation Procedure Evacuation is the most important part of the entire service procedure. The life and efficiency of the equipment is dependent upon the thoroughness exercised by the serviceman when evacuating air and moisture from the system. Air or nitrogen in the system causes high condensing temperatures and pressure, resulting in increased power input and nonverifiable...
START-UP Checking Refrigerant Charge Charge for all systems should be checked against Supply airflow must be between 320 and 450 cfm per rated cooling ton prior to adjusting system the Charging Chart inside the access panel cover. charge. If a humidification system is installed, WARNING: The top of the scroll disengage it from operation prior to charge...
START-UP Checking Refrigerant Charge (cont.) With an accurate scale (+/– 1 oz. [28.3 g]) or 2. Note the Outdoor Dry Bulb Temperature, volumetric charging device, adjust charge ODDB° = _____°F [_____°C]. Unit charging is difference between that shown on the unit data recommended under the following outdoor conditions ONLY: plate and that calculated for the new system...
START-UP Checking Refrigerant Charge (cont.) conditions, add charge. If the measured subcool NOTICE: If the indoor temperature is is above the listed requirement for the given above or below the recommended range, run the outdoor and indoor conditions, remove charge. system to bring the temperature down or run the electric heat/furnace to bring the temperature Finishing Up Installation...
COMPONENTS AND CONTROLS Compressor Crankcase Heat (CCH)* While scroll compressors usually do not require • When a low ambient control is used for system crankcase heaters, there are instances when a operation below 55°F. heater should be added. Refrigerant migration All heaters are located on the lower half of the during the off cycle can result in a noisy start up.
COMPONENTS AND CONTROLS High- and Low-Pressure Controls (HPC and LPC) HPC and LPC are not installed on FO****C***A, CAUTION: The compressor has but can be field installed using the followiing an internal overload protector. Under some kit numbers: RXAB-A0z (high pressure control) conditions, it can take up to 2 hours for this and RXAC-A0Z (low pressure control).
ACCESSORIES Time Delay Control WARNING: Turn off electric power at the fuse box or service panel before making (Part No. RXMD-B01) any electrical connections. Also, the ground The time delay control is in the low voltage control connection must be completed before making line circuit.
DIAGNOSTICS Electrical Checks Flowchart Unit Running? Go to Mechanical Checks for Cooling or Heating Thermostat Problem? Repair and Recheck Transformer Problem? Repair and Recheck Voltage on Compressor Side of Contactor? Voltage on Line Run Capacitor Side of Contactor? Start Capacitor Circuit Breakers or Fuses Open Compressor...
DIAGNOSTICS General Troubleshooting Chart WARNING: Disconnect all power to unit before servicing. Contactor may break only one side. Failure to shut off power can cause electrical shock resulting in personal injury or death. SYMPTOM POSSIBLE CAUSE REMEDY Unit will not run •...
DIAGNOSTICS Service Analyzer Charts COMPRESSOR OVERHEATING SYMPTOM POSSIBLE CAUSE CHECK/REMEDY High superheat Low charge Check system charge. (greater than 15°F Faulty metering device Restricted cap tube, TEV (TXV) [-9°C] at coil) Power element superheat out of adjustment internally Foreign matter stopping fl ow High internal load Hot air (attic) entering return Heat source on;...
Page 42
DIAGNOSTICS Service Analyzer Charts COMPRESSOR OVERHEATING (cont.) SYMPTOM POSSIBLE CAUSE CHECK OR REMEDIES Short cycling of Low charge Check system charge. compressor (cont.) Low evaporator airfl ow Dirty coil Dirty fi lter Duct too small or restricted Faulty run capacitor Replace.
Page 43
DIAGNOSTICS Service Analyzer Charts CONTAMINATION SYMPTOM POSSIBLE CAUSE REMEDY Moisture Poor evacuation on installation or during service In each case, the cure is the same. Recover refrigerant. Add fi lter drier, evacuate, and recharge. High head pressure Noncondensibles air Unusual head and Wrong refrigerant or mixed refrigerants suction readings Foreign matter –...
Page 44
DIAGNOSTICS Service Analyzer Charts FLOODING SYMPTOM POSSIBLE CAUSE REMEDY Loose sensing bulb Secure the bulb and insulate. Bulb in wrong location Relocate bulb. Poor system control using a TEV Wrong size TEV Use correct replacement. Improper superheat setting (less than 5°F [-15°C]) Replace TEV.
Page 45
DIAGNOSTICS Service Analyzer Charts THERMOSTATIC EXPANSION VALVES (cont.) SYMPTOM POSSIBLE CAUSE REMEDY Refrigerant drainage from fl ooded evaporator Install trap riser to the top of the evaporator coil. Inoperable crankcase heater or crankcase heater Replace or add crankcase heater. Compressor fl ood needed back upon start-up Any of the causes listed under symptoms of...
DIAGNOSTICS COOLING MODE TROUBLESHOOTING TIPS INDICATORS DISCHARGE SUCTION SUPERHEAT COMPRESSOR SYSTEM SUBCOOLING PRESSURE PRESSURE Normal: AMPS PROBLEM Normal: See 5°–15°F Charging Chart [-15° – -9°C] High High High High Overcharge High Undercharge Liquid Restriction High High (Drier) Low Indoor Airfl ow High High High...