Simulation - Siemens SITRANS F FC410 Operating Instructions Manual

Coriolis flowmeters with modbus
Table of Contents

Advertisement

Functions

7.8 Simulation

The access levels are:
● Read Only
Allows no configuration. The user is only able to view the parameter values. No PIN code
is required.
● User
Allows configuration and service of all parameters except calibration parameters. Default
PIN code is 2457.
Note
Auto Log Off function
The access level will be set to Read Only mode if the device is powered off
7.8
Simulation
Simulation is used for testing purposes, typically for checking that the readings of the control
system are correct.
Process value simulation
The following process values can be simulated:
● Massflow (Modbus address 2764)
● Density (Modbus address 2766)
● Process Media Temperature (Modbus address 2768)
● Frame Temperature (Modbus address 2770)
● Volumeflow (Modbus address 2772)
The simulation can be activated through SIMATIC PDM in the menu Device → Simulation →
Process Variables.
76
Operating Instructions, 02/2016, A5E33120874-AC