10-9-3. Wiring Specifications
Number of wires
2
• A 2-wire non-polarity cable is used.
• The cable length depends on each central control system.
• When used in a system including multiple air conditioners, the length includes the length of all wires between
indoor and outdoor units on the side of multiple air conditioners.
• Use 2-wire shield cable (MVVS) to protect from noise.
• Joint shield wire between indoor units by closed-end terminating, and leave its end open with insulation
processing. Make one-point grounding at the indoor unit side. Set the terminating resistors.
(Central control for custom indoor units only)
Central control device
U1 U2
Outdoor unit
1 2 3
Indoor unit
U3 U4
1 2 3
A B
Remote controller
Size
Up to 1000 m: 1.25 mm² stranded wires
Up to 2000 m: 2.0 mm² stranded wires
Notes
1 Joint shield wire between indoor units by closed-end terminating.
2 Leave the end of the shield wire open with insulation processing.
3 Make one-point grounding at the indoor unit side.
1 2 3
Follower unit
Header unit
U3 U4
1 2 3
A B
Remote controller
Remote controller
(Group operation)
Specification
Central control system wiring
1 2 3
1 2 3
Follower unit
Header unit
1 2 3
1 2 3
A B
A B
Remote controller
(Triple operation)
- 75 -
MVVS
: TCC-LINK adapter (option)
Required for DI-SDI indoor units
other than Wall Type
Follower unit
U3 U4
1 2 3
1 2 3
A B
A B
Earth screw