10-6. Monitor Function of Remote Controller Switch

n Calling of sensor temperature display
<Contents>
Each data of the remote controller, indoor unit and outdoor unit can be understood by calling the service
monitor mode from the remote controller.
<Procedure>
1
CL
Push
TEST
+
buttons simultaneously for 4 seconds to
call the service monitor mode.
The service monitor goes on, the master indoor unit No. is
displayed at first and then the temperature of CODE No.
is displayed.
2
Push temperature set
the CODE No. of data to be monitored.
The CODE No. list is shown below.
CODE No.
Room temperature under control ∗1
00
01
Room temperature
(Remote controller)
02
Indoor suction temperature (TA)
03
Indoor heat exchanger (Coil)
temperature (TCJ)
04
Indoor heat exchanger (Coil)
temperature (TC)
3
Push
button to select the indoor unit to be monitored.
U NIT L OU VE R
Each data of the indoor unit and its outdoor units can be monitored.
4
Pushing
TE ST
button returns the status to the usual display.
ò
TEMP.
buttons and then change
Data name
ò
ò

2
<Operation procedure>
1
CODE No.
60
Outdoor heat exchanger (Coil) temperature (TE)
61
Outside temperature (TO)
62
Compressor discharge temperature (TD)
63
Compressor suction temperature (TS)
65
Heat sink temperature (TH)
∗1 Header indoor unit only under group control.
- 71 -
TEMP.
O N / O F F
TIMER S E T
FAN
M O D E
TIME
SAVE
A A
VENT
FILTER
L L
RE S E T
TE ST
S E T
CL
S WIN G/ FI X
U NI T LOUVER
T
4
1
3
2
3
4
Returned to usual display
Data name

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rav-gm901krtp-eRav-gm901krtp-tr

Table of Contents