Fan speed is defined by outdoor temperature and compressor frequency.
• Outside air temperature zone selection
Fan step
S-HIGH2
S-HIGH1
HIGH
10
9
8
7
6
5
4
3
2
1
NOTE: After defrost control on the heating mode, the fan speed is kept higher regardless of the
compressor frequency.
Fan speed after defrost control: 1,100 rpm
3-2. Outdoor fan control
Outside air
temperature rises
21°C
12°C
2°C
Cooling
Heating
Y zone
1,100
1,050
1,100
1,050
1,100
1,100
1,050
1,100
810
870
810
760
560
760
560
680
440
530
440
500
440
420
440
420
Outside air
temperature drops
Y zone
Z zone
F zone
G zone
Dry
Cooling or dry at low outdoor temp.
Y zone
Z zone
1,050
850
810
850
810
770
560
630
560
440
440
320
440
320
440
320
440
320
- (04-14) -
19°C
10°C
0°C
Unit: rpm
F zone
G zone
320
320
320
270
270
270
270
270
270
270
270
270
230
230
230
230
230
230
3. Fan control