• Heating mode
Model name
AOUG09LZAH1
AOUG12LZAH1
AOUG15LZAH1
1-5. Compressor frequency limitation by outdoor temperature
F zone
66.2°F
(19°C)
E zone
41.0°F
(5°C)
D zone
32.0°F
(0°C)
C zone
5.0°F
(-15°C)
B zone
-13.0°F
(-25°C)
A zone
Outdoor temperature zone
A zone
B zone
C zone
D zone
E zone
F zone
A zone
B zone
C zone
D zone
E zone
F zone
- (04-6) -
Limitation of compressor
frequency
34 rps
34 rps
34 rps
15 rps
14 rps
14 rps
30 rps
30 rps
30 rps
13 rps
10 rps
10 rps