Low-profile modular crescent cuber
Table of Contents

Advertisement

2. Checks Before Installation

1) Remove the shipping carton, tape, and packing material.
2) Check that the refrigerant lines do not rub or touch lines or other surfaces, and that the
fan blade moves freely.

3. Setup

1) Assemble two sets of legs using the legs, bolts, and nuts provided. See Fig. 11.
2) Position one of the plates provided between a set of legs and the remote condenser
unit, then secure the legs to the remote condenser unit with the bolts and nuts provided.
Repeat on the other side with the remaining set of legs.
3) The bottom of each leg has a mounting hole. Secure the legs to the permanent site with
4 bolts (not included).

4. Line Set Size and Refrigerant Charge

The icemaker, line set, and remote condenser unit must contain the same type
of refrigerant. Mixing of refrigerants will result in improper operation and possible
damage to the refrigeration system.
Hoshizaki
Remote
Hoshizaki
Condenser
Icemaker
Unit
KML-700MRJZ URC-9FZ
Bolt with Split Lock
Washer and Flat Washer
Plate
Nut
Fig. 11
NOTICE
Line Set Size and Refrigerant Charge
Line Set
Up to 66' (20 m)
Liquid
Discharge
Line
Line
3/8"
1/2" OD
OD
23
Nut
Leg
Line Set
Greater than 66' (20 m)
Maximum 100' (30.5 m)
Charge
Liquid
Discharge
Adjustment
Line
Line
Not
3/8"
1/2" OD
Applicable
OD
Bolt with Split Lock
Washer and Flat Washer
Charge Adjustment
(R-404A)
Add 0.4 oz. for each
foot over 66' (40 g
for each meter over
20 m). Write new
total charge on
icemaker's rating
label.