Gauge Pressure With Front-Flush Diaphragm - Siemens SITRANS 7MF03.0 Compact Operating Instructions

Pressure transmitter
Hide thumbs Also See for SITRANS 7MF03.0:
Table of Contents

Advertisement

Technical data
7.2 Measuring accuracy of SITRANS P320
Effect of mounting position
In pressure per change of angle
0.04 kPa/0.4 mbar/0.006 psi per 10° incline
(zero-point correction is possible with position error compen‐
sation)
7.2.7

Gauge pressure with front-flush diaphragm

Conformity error at limit point setting, including hysteresis and repeatability - gauge pressure with front-flush diaphragm
Measuring span ratio r (spread, Turn-Down)
● Linear characteristic curve
Effect of ambient temperature - gauge pressure with front-flush diaphragm
In percent per 28 °C (50 °F)
Long-term stability at ±30 °C (±54 °F) - gauge pressure with front-flush diaphragm
1 bar/100 kPa/14.5 psi
4 bar/400 kPa/58 psi
16 bar/1.6 MPa/232 psi
63 bar/6.3 MPa/914 psi
Step response time T
(without electrical damping) - gauge pressure with front-flush diaphragm
63
Approx. 0.105 s
Effect of mounting position - gauge pressure with front-flush diaphragm
≤ 0.4 mbar/0.04 kPa/0.006 psi per 10° incline
(zero-point correction is possible with position error compen‐
sation)
68
1 bar/100 kPa/14.5 psi
4 bar/400 kPa/58 psi
16 bar/1.6 MPa/232 psi
63 bar/6.3 MPa/914 psi
1 bar/100 kPa/14.5 psi
4 bar/400 kPa/58 psi
16 bar/1.6 MPa/232 psi
63 bar/6.3 MPa/914 psi
r = max. measuring span/set measuring span and nominal
measuring range
r ≤ 5
≤ 0.075%
≤ (0.08 • r + 0.16)%
In 5 years ≤ (0.25 • r)%
In 5 years ≤ (0.125 • r)%
Compact Operating Instructions, 06/2018, A5E38874562-AA
5 < r ≤ 100
≤ (0.005 • r + 0.05)%
SITRANS P320/P420 (mA/HART)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans p420Sitrans p320Sitrans 7mf04.0

Table of Contents