Pressure Adjustment; Start Up And Test - Follett Horizon HCD1000R Series Installation Instructions Manual

Hide thumbs Also See for Horizon HCD1000R Series:
Table of Contents

Advertisement

5.1
Check pressure adjustment
1. The pressure control is located in the electrical box near the refrigeration line set
connection point.
2. Verify the control is set for system operation of 10 psi cut out and 30 psi cut in
3. If adjustment is needed always adjust the cut in fi rst.
Ice machine MUST be cleaned and sanitized prior to operation!
Consult Operation and Service Manual provided with ice machine for cleaning and sanitizing instructions.
6.1
Verify operation
• Turn dispenser power ON if
applicable
• Check current draw of compressor
to verify correct electrical
operation
• Put a piece of ice on bin
thermostat or hold a cup under
the shuttle actuator on the bin/
dispenser to verify that the
evaporator unit shuts OFF;
condensing unit pumps down and
shuts off.
• After shut off, restart the ice
machine
REMOTE CONDENSING UNIT
NOTICE
Horizon Condenser Unit Compressor Amperage
Single-Phase
Model Number
1000R
00168054
1400R
00178640
1650R
00973925
3-Phase
Model Number
1000R
00990200
1400R
00990218
1650R
00990226

Pressure adjustment

Start up and test

Compressor
Running amps (+/- 10%)
AJA7490ZXD
AWA9517ZXN
AVA9522ZXN
Compressor
Running amps (+/- 10%)
AWA9490ZXTHN
AWA9517ZXTHN
AVA9522ZXTHN
5
6
7.4
14.7
22.6
4.7
7.3
10.3
7