Bryant 926TC Installation, Start-Up, Operating And Service And Maintenance Instructions page 18

Two-stage, non-communicating, variable 25-speed, ecm multipoise, condensing gas furnace with intelisense
Table of Contents

Advertisement

926TC: Installation, Start-up, Operating and Service and Maintenance Instructions
CAUTION
!
MINOR PROPERTY HAZARD
Failure to follow this caution may result in minor property damage.
Local codes may require a drain pan under entire furnace and
condensate trap when a condensing furnace is used in an attic
application or over a finished ceiling.
WARNING
!
FIRE, EXPLOSION, AND CARBON MONOXIDE
POISONING HAZARD
Failure to follow this warning could result in personal injury, death, or
property damage.
Do not install the furnace on its back or hang furnace with control
compartment facing downward. Safety control operation will be
adversely affected. Never connect return-air ducts to the back of the
furnace.
The furnace can be installed horizontally in an attic or crawlspace on
either the left-hand (LH) or right-hand (RH) side. The furnace can be
hung from floor joists, rafters or trusses or installed on a
non-combustible platform, blocks, bricks or pad.
Supply Air Connections
For a furnace not equipped with a cooling coil, the outlet duct shall be
provided with a removable access panel. This opening shall be
accessible when the furnace is installed and shall be of such a size that
FURNACE
CASING WIDTH
IN. (mm)
Upflow Applications on Combustible or Noncombustible Flooring
Downflow Applications on Noncombustible Flooring
*
14–3/16
Downflow applications on combustible flooring
(360)
Downflow Applications on Combustible Flooring with coil assembly or
Upflow Applications on Combustible or Noncombustible Flooring
Downflow Applications on Noncombustible Flooring
17–1/2
(445)
Downflow applications on combustible flooring
Downflow Applications on Combustible Flooring with coil assembly or
Upflow Applications on Combustible or Noncombustible Flooring
Downflow Applications on Noncombustible Flooring
21
(533)
Downflow applications on combustible flooring
Downflow Applications on Combustible Flooring with coil assembly or
Upflow Applications on Combustible or Noncombustible Flooring
Downflow Applications on Noncombustible Flooring
24-1/2
(622)
Downflow applications on Combustible flooring
Downflow Applications on Combustible Flooring with coil assembly or
*. Not all families have these models
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Table 6 – Opening Dimensions - in. (mm)
APPLICATION
(subbase not required)
(subbase not required)
(subbase required)
coil box (subbase not required)
(subbase not required)
(subbase not required)
(subbase required)
coil box (subbase not required)
(subbase not required)
(subbase not required)
(subbase required)
coil box (subbase not required)
(subbase not required)
(subbase not required)
(subbase required)
coil box (subbase not required)
the heat exchanger can be viewed for possible openings using light
assistance or a probe can be inserted for sampling the air stream. The
cover attachment shall prevent leaks.
Connect supply-air duct to flanges on furnace supply-air outlet. Bend
flange upward to 90° with wide duct pliers. See
duct must be connected to ONLY the furnace supply-outlet-air duct
flanges or air conditioning coil casing (when used). DO NOT cut main
furnace casing side to attach supply air duct, humidifier, or other
accessories. All supply-side accessories MUST be connected to duct
external to furnace main casing.
Return Air Connections
The return-air duct may be connected to bottom of the furnace. The side
of casing that faces downward may also be used for return air
connection. A combination of the bottom and downward facing side may
also be used. The upward facing side of the casing cannot be used as a
return air connection. See
Fig.
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom
return-air opening. Remove and discard this panel when bottom return
air is used. To remove bottom closure panel see
Side Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom
return-air opening. This panel MUST be in place when side return air
inlet(s) are used without a bottom return air inlet.
Not all horizontal furnaces are approved for side return air connections
See
Fig.
23. Where required by code, seal bottom closure to furnace with
tape, mastic or other durable sealing method.
PLENUM OPENING
A
12-11/16
(322)
12-9/16
(319)
11-13/16
(300)
12-5/16
(313)
16
(406)
15-7/8
(403)
15-1/8
(384)
15-1/2
(394)
19-1/2
(495)
19-3/8
(492)
18-5/8
(473)
19
(483)
23
(584)
22-7/8
(581)
22-1/8
(562)
22-1/2
(572)
18
Fig.
20. The supply-air
23.
Fig.
24.
FLOOR OPENING
B
C
21-5/8
13-5/16
(549)
(338)
19
13-3/16
(483)
(335)
19
13-7/16
(483)
(341)
19
13-5/16
(483)
(338)
21-5/8
16-5/8
(549)
(422)
19
16-1/2
(483)
(419)
19
16-3/4
(483)
(425)
19
16-1/2
(483)
(419)
21-5/8
20-1/8
(549)
(511)
19
20
(483)
(508)
19
20-1/4
(483)
(514)
19
20
(483)
(508)
21-5/8
23-5/8
(549)
(600)
19
23-1/2
(483)
(597)
19
23-3/4
(483)
(603)
19
23-1/2
(483)
(597)
D
22-1/4
(565)
19-5/8
(498)
20-5/8
(524)
20
(508)
22-1/4
(565)
19-5/8
(498)
20-5/8
(524)
20
(508)
22-1/4
(565)
19-5/8
(498)
20-5/8
(524)
20
(508)
22-1/4
(565)
19-5/8
(498)
20-5/8
(524)
20
(508)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents