Samsung AR36BSHUMGMX Installation Manual page 25

Table of Contents

Advertisement

Option
Input
SEG1 SEG2 SEG3 SEG4
item
unit
Current
restriction
Main
0
rate
¹⁾
Dedicated
mode for
Main
0
cooling/
heating
• ¹⁾
Current restriction rate : When restriction option is
set, cooling and heating performance may decrease.
CAUTION
• Edited option will not be saved if you do not end the
option setting as explained in above instruction.
※ While you are setting the option, you may press and hold
the K1 button to reset the value to previous setting.
※ If you want to restore the setting to factory default,
press and hold the K4 button while you are in the
option setting mode.
– If you press and hold the K4 button, setting will be
restored to factory default but it doesn't mean that
restored setting is saved. Press and hold the K2
button. When the segments shows that tracking
mode is in progress, setting will be saved.
Step 15. Auto check(Installation
commissioning mode)
• This is a self-diagnosis function to determine the
installation status and product integrity in the initial
installation.
(This model requires the Auto check to be
implemented in the installation step before its normal
operation is initiated.)
• Procedures of Auto check
DB68-11579A-00_IM_RAC oudoor_AA_EN_.indd 25
DB68-11579A-00_IM_RAC oudoor_AA_EN_.indd 25
Function
100%
0
0
(Factory
default)
0
1
95%
0
2
90%
0
3
85%
0
4
80%
6
0
5
75%
0
6
70%
0
7
65%
0
8
60%
0
9
55%
1
0
50%
1
1
100%
Cooling /
Heating
0
0
operation
(default)
7
Cooling
0
1
operation only
Heating
0
2
operation only
1 Check the product installation status.
– Check the power supply, communication cables,
service valve openings, and quantity of additional
refrigerant.
– In the initial power supply after installation, the
warning of non-fulfilment of Auto check (
be indicated on the outdoor unit and the system
will not function properly.
2 Enter the mode of Auto check.
– Press the K2 button 7 times consecutively.
– During the Auto check, the display will show "
" BLANK" "BLANK" and it will take about 10 to 30
minutes for completion.
3 The mode of Auto check will then be completed.
– Successful Auto check: After checking the blinking
that indicates installation completion on the display
(
), press the K1 or K2 button to turn the
status to the standby mode for normal operation.
– Failure of Auto check: An error code blinks on
the display. Resolve the error by referring to the
details on the Troubleshooting page about how to
troubleshoot for each error code, and then perform
the Auto check again.
NOTE
• If you intend to install more refrigerant piping prior
to entering the mode of Auto check, make sure
that the refrigerant to be added meets the related
requirements.
In this process, it is possible to test the cooling test
mode (K2 switch: once) and heating test mode (K1
switch: once).
• You may stop the mode of test operation for installation
by pressing the K3 switch during the test operation.
(After it stops,
(the warning of incomplete Auto
check) will be displayed)
• During the Auto check, it is possible to refer to the
system status by pressing the K4 switch.
• In the case that there is an error during the Auto check,
the Auto check will stop. In this case, take a measure for
the error and then try the test operation again.
• If the test operation is not completed properly, the
product will not function in the intended way.
(no implementation of Auto check) will be
displayed. Be sure to solve the trouble and complete
the test operation for installation properly.
indicates, not that the unit is out of order, but
that the Auto check has yet to be implemented as an
essential step of installation.
) will
" "
25
English
2022-01-12 오후 1:37:53
2022-01-12 오후 1:37:53

Advertisement

Table of Contents
loading

Table of Contents