Samsung AR36BSHUMGMX Installation Manual page 11

Table of Contents

Advertisement

Main power terminal block specifications
• 1-phase
AC power :
M4 screw
1(L)
2(N)
0.59(15)
0.47(12)
Model
Outdoor
AR36BSHUMGMX
AR36BSHUMGMN
NOTE
• RLA is based on AHRI 210/240 cooling standard
condition [Indoor temp. : 26.7 °C / 80 °F(DB) / 19.46 °C /
67 °F(WB), Outdoor temp. : 35 °C / 95 °F(DB)]
• Voltage tolerance is ± 10 %.
• Maximum allowable voltage between phases is 2 %.
• Symbols
– RLA: Rated Load Ampere (A)
– MOC: Maximum Operating Current (A)
– MCA: Minimum Circuit Ampere (A)
– MOP: Maximum Overcurrent Protective Device (A)
• Voltage range
– Units are suitable for use on electrical systems
where voltage supplied to unit terminal is not
below or above listed range limits.
• Maximum allowable voltage variation between phases
is 2%.
• Wire size & type must comply with the applicable local
and national code.
– Wire size: Based on the value of MCA.
– Wire type:
1-phase: 60245 IEC57(IEC) or H05RN-F(CENELEC)
grade or more
DB68-11579A-00_IM_RAC oudoor_AA_EN_.indd 11
DB68-11579A-00_IM_RAC oudoor_AA_EN_.indd 11
[Unit : inch(mm)]
Communication :
M4 screw
F1
F2
L
N
0.40(10.1)
0.45(11.4)
Power Source
Indoor
208~230V/60Hz
Main power cable specifications
The power cable is not supplied with air conditioner.
• Select the power supply cable in accordance with
relevant local and national regulations.
• Wire size must comply with the applicable local and
national code.
• Specifications for local wiring power cord and branch
wiring are in compliance with local cord.
Outdoor
RLA
MOC
(A)
FAN1(A)
FAN2(A)
14.7
1.25
1.25
Connecting the outdoor-to-indoor power cable
and the communication cable
1(L)
1(L)
2(N)
Main power cable
Outdoor to indoor power cable
Indoor
Rated input
current of
MCA
MOP
the power
(A)
(A)
conversion
equipment
FAN(A)
0.51
21.4
35.0
Indoor Unit
2(N)
F1
F2
Cable clamp
Outdoor Unit
L
N
Cable tie
Communication cable
English
2022-01-12 오후 1:37:50
2022-01-12 오후 1:37:50
11