2 Select the insulation of the refrigerant pipe.
• Insulate the gas side and liquid side pipe referring
to the thickness according to the pipe size.
• Less than Indoor temperature of 86℉(30℃) and
humidity of 85% is the standard condition. If
installing in a high humidity condition, use one
grade thicker insulator by referring to the table
below. If installing in an unfavourable conditions,
use thicker one.
• Insulator's heat-resistance temperature should be
more than 248℉(120℃).
Outer diameter
Pipe
mm
inch
6.35~9.52
1/4~3/8
Liquid
pipe
12.7~50.80
1/2~2
6.35
1/4
9.52~25.4
3/8~1
Gas
pipe
1 1/8~1
28.58~44.45
3/4
50.8
2
• When installing insulation in places and
conditions below, use the same insulation that is
used for high humidity conditions.
<Geological condition>
– High humidity places such as shoreline, hot spring,
near lake or river, and ridge (when the part of the
building is covered by earth and sand.)
<Geological condition>
– Restaurant ceiling, sauna, swimming pool etc.
– <Building construction condition>
– The ceiling frequently exposed to moisture and
cooling is not covered.
– e.g. The pipe installed at a corridor of a dormitory
and studio or near an exit that opens and closes
frequently.
– The place where the pipe is installed is highly
humid due to the lack of ventilation system.
DB68-11579A-00_IM_RAC oudoor_AA_EN_.indd 21
DB68-11579A-00_IM_RAC oudoor_AA_EN_.indd 21
Insulation Type
(Cooling, Heating)
General
High humidity
[86°F(30°C),
[86°F(30°C),
Remarks
85%]
over 85%]
EPDM, NBR
mm
inch
mm
inch
9
3/8
9
3/8
13
1/2
13
1/2
Heating
13
1/2
19
3/4
resisting
temperature
19
3/4
25
1
over
248°F(120°C)
19
3/4
32
1 1/4
25
1
38
1 1/2

Step 13 Checking the earthing

If the power distribution circuit does not have a earthing
or the earthing does not comply with specifications, an
earthing electrode must be installed. The corresponding
accessories are not supplied with the air conditioner.
1 Select an earthing electrode that complies with the
specifications given in the illustration.
2 Connect the flexible hose to the flexible hose port.
• In damp hard soil rather than loose sandy or
gravel soil that has a higher earthing resistance.
• Away from underground structures or facilities,
such as gas pipes, water pipes, telephone lines
and underground cables.
• At least 6.6 ft away from a lightening conductor
earthing electrode and its cable.
NOTE
• The earthing wire for the telephone line cannot be
used to ground the air conditioner.
Carbon plastic
To grounding screw
19.69inch(50cm)
11.81inch
(30cm)
3 Finish wrapping insulating tape around the rest of the
pipes leading to the outdoor unit.
4 Install a green/yellow color earthing wire:
• If the earthing wire is too short, connect an
extension lead in a mechanical way and wrap it
with insulating tape (do not bury the connection).
• Secure the earthing wire in position with staples.
NOTE
• If the earthing electrode is installed in an area with
heavy traffic, its wire must be connected securely.
5 Carefully check the installation by measuring the
earthing resistance with a earth resistance tester. If
the resistance is above the required level, drive the
electrode deeper into the ground or increase the
number of earthing electrodes.
6 Connect the earthing wire to the electrical component
box inside of the outdoor unit.
Steel core
Terminal M4
PVC-insulated
green/yellow
wire
21
English
2022-01-12 오후 1:37:52
2022-01-12 오후 1:37:52