Installation Procedure
-
After short push 1
After short push 2
K4 long
push
After short push 3
After short push 4
Long push K4 (Main micom ver.) → short push 1 more (Inv. micom ver.) → short push 1 more (E2P. ver.) → short push 1
more (Automatic address) → short push 1 more (Manual address) → short push 1 more (Main micom ver.) → ....... → Long
push K4 (View mode end)
7 Setting outdoor unit option switch and address manually
a Setting the option
• Press and hold K2 to enter the option setting.
(Only available when the operation is stopped)
– If you enter the option setting, display will show
the following.
– Seg 1 and Seg 2 will display the number for
selected option.
– Seg 3 and Seg 4 will display the number for set
value of the selected option.
• If you have entered option setting, you can shortly
press the K1 switch to adjust the value of the Seg 1,
Seg 2 and select the desired option.
Example)
• If you have selected desired option, you can shortly
press the K2 switch to adjust the value of the Seg 3,
Seg 4 and change the function for the selected option.
Example)
24
English
DB68-11579A-00_IM_RAC oudoor_AA_EN_.indd 24
DB68-11579A-00_IM_RAC oudoor_AA_EN_.indd 24
Display contents
SEG1
Main micom version
Year (Dec)
Inverter micom version
Year (Dec)
E2P version
Year (Dec)
Page 2 - (SEG1,2 - Indoor : "A","0") (SEG3,4 - Address : ex) 00)
Page 2 - (SEG1,2 - Indoor : "A","0") (SEG3,4 - Address : ex) 00)
SEG2
Month (Hex)
Date (Tens digit) Date (Units digit)
Month (Hex)
Date (Tens digit) Date (Units digit)
Month (Hex)
Date (Tens digit) Date (Units digit)
Page 1 - AUTO
Page 1 - MANU
• After selecting the function for options, press and
hold the K2 switch for 2 seconds. Edited value of
the option will be saved when entire segments
blinks and tracking mode begins.
Option
Input
SEG1 SEG2 SEG3 SEG4
item
unit
Channel
Main
0
0
address
Snow
accumulation
Main
0
1
prevention
control
Step for
Main
0
2
Silence mode
Type of
Main
0
3
Silence mode
Temperature
Main
0
4
unit
Not applicable Main
0
5
SEG3
SEG4
Function
Automatic
setting
A
U
(Factory
default)
Manual
00~15
setting
Disabled
0
0
(Factory
default)
0
1
Enabled
Disabled
0
0
(Factory
default)
0
1
Step1
0
2
Step2
0
3
Step3
Automatic
Silence mode
0
0
(Factory
default)
Manual
0
1
Silence mode
Celsius
0
0
(default)
0
1
Fahrenheit
0
0
Not applicable
0
1
Not applicable
2022-01-12 오후 1:37:53
2022-01-12 오후 1:37:53