Terminal
Terminal function
symbol
24V DC common for
P24
digital inputs
10V reference voltage
H
for analog set value
(using potentiometer)
Frequency set value
O
analog input (0-10V)
Frequency set value
OI
analog input (4-20mA)
Common terminal
L
for analog set value
inputs
FM
Frequency monitor
L
0V
FA1
Frequency arrival
(01)
signals
FA2
(02)
RUN
RUN signal
(00)
OL
Overload signal
(03)
OD
PID deviation signal
(04)
AL
Alarm signal
(05)
CM2
0V
AL0
Alarm terminals
AL1
AL2
Common terminal for the intelligent digital inputs
Set value configured
Set value configured
using potentiometer:
using voltage input:
H
O OI
L
Pot (1k – 2K)
0 - 9,6V DC (rated value 10V)
Input impedance 10k Ohms
The OI input (set value using analog current 4..20mA) will only be used if
the input configured as AT has been closed before. If no digital input has
been configured as an AT input then the set values that are present at termi-
nals O and OI will be added.
Using the FM output the output frequency can be monitored and displayed using
an external analog or digital meter. If needed, the motor current can be displayed
Common terminal for the FM output
Frequency
f
soll
FA1 active
When a digital output is configured as FA1 then a signal
is output as long as the output frequency is held constant
at set value. With a digital output being configured as
FA2, a signal will be output as long as the actual output
frequency is above the values set under C 42 and C 43.
The RUN signal is active as long
as the motor is running.
The OL signal will be output when the actual motor current
is above the threshold set under C 41.
The OD signal will be output when the threshold set under
C 44 (level of PID deviation) is being passed.
The alarm signal is output in case a trip condition occurs.
This is the 0V common for the programmable digital outputs 11 and 12. These
open collector type outputs are isolated using photocouplers and are separated
During normal trouble-free operation the terminals AL0 and AL1 are shorted.
During a trip condition or while power to the inverter is off the terminals AL0 and
Absolute maximum relay contact ratings:
250VAC; max. load of 2.5A (purely resistive) or 0.2A (at an cos phi of 0.4)
30VDC; max. load of 3.0A (purely resistive) or 0.7A (at an cos phi of 0.4)
Minimum relay contact ratings:
100VAC at a load of 10mA or 5VDC at a load of 100mA
7-2
Chapter 7 – Control circuit terminal functions
Description
Set value configured
using current input:
H
O OI
L
4 - 19,6mA DC (rated value 20mA)
Input impedance 250 Ohms
instead of the frequency.
Frequency
f
2
f
1
FA2 active
from L common.
AL2 are shorted instead.
H
O OI L
Connection of a
signal relay to digital
output 11 or 12:
12 11
CM2
Open collector
type output
(max. 27VDC, 50mA)