Wiring equipment and options

CAUTION
Provide the wiring equipment in accordance with the safety codes required by
jurisdictional authorities. If specified in standards or laws and regulations, follow
their istructions. In the following table some guidelines for choosing an appropriate
wire gauge are presented:
Motor
output
(kW)
0.2
0.4
0.55
0.75
1.1
1.5
2.2
3.7
5.5
7.5
0.4
0.75
1.5
2.2
3.0
4.0
5.5
7.5
Notes:
-
Field wiring connections must be made by a UL listed and CSA certified closed-loop terminal connector
sized for the wire gauge involved. The connector must be fixed using the crimp tool specified by the
connector manufacturer.
-
Only use a fuse that has the appropriate rated current.
-
Be sure to use bigger wires for mains circuit cables and motor cables if the distance exceeds 20m.
*)
2
Use 0,75mm
for the alarm signal wire. The wire stripping length should be approximately 5–6 mm. The
wire sleeve diameter except for the alarm signal wire should not be greater than 2mm.
Cable specifications
Inverter
model
Power lines
L100-002NFE
L100-002NFU
1.5 mm
L100-004NFE
(AWG 15)
L100-004NFU
L100-005NFE
L100-007NFE
2.5 mm
L100-007NFU
(AWG 13)
L100-011NFE
L100-015NFE
4.0 mm
L100-015NFU
(AWG 11)
L100-022NFE
4.0 mm
L100-022NFU
(AWG 11)
4.0 mm
L100-037LFU
(AWG 11)
L100-055LFE
6.0 mm
L100-055LFU
(AWG 9)
L100-075LFE
10 mm
L100-075LFU
(AWG 8)
L100-004HFE
L100-004HFU
L100-007HFE
L100-007HFU
1.5 mm
(AWG 15)
L100-015HFE
L100-015HFU
L100-022HFE
L100-022HFU
L100-030HFE
2.5 mm
L100-040HFE
(AWG 13)
L100-040HFU
L100-055HFE
L100-055HFU
4.0 mm
(AWG 11)
L100-075HFE
L100-075HFU
5-5
600V fuse to be
Signal
(rated current / A)
lines
2
2
2
25 A (single phase)
16 A (three phase)
2
40 A (single phase)
25 A (three phase)
2
2
2
2
2
2
Chapter 5 – Wiring
used
10 A
16 A
40 A
40 A
60 A
10 A
16 A
25 A