TROUBLESHOOTING
PROBLEM
Engine runs erratically
or does not hold steady
speed.
41
POTENTIAL CAUSE
1.
Power demand of connected
240-Volt AC load may be
varying.
2.
If output indicator and
overload alarm are both
illuminated, there is an
overload in the connected
240-Volt AC load.
3.
Engine is not warm enough.
4.
Choke control is in the
START or CHOKE position
and engine is already warm
or hot.
5.
Fuel is stale or
contaminated.
6.
Air filter is dirty or blocked.
7.
If above possible causes
are checked and eliminated,
generator may be faulty.
SOLUTION
1.
Engine speed varies when electrical load changes;
this is normal operation. It is most noticeable when
ECO throttle switch is in the ON position. No fault.
2.
Switch off or unplug connected 240-Volt AC
device(s) to reduce electrical power demand.
3.
Disconnect all electrical cords and appliances from
generator. Allow engine to run for at least 2 minutes
after the choke control has been moved to the RUN
or ON position before reconnecting electrical loads.
4.
Move choke control to the RUN or ON position.
5.
Drain fuel and refill with fresh fuel.
6.
Check air filter element and clean if necessary.
7.
Take generator to an authorised Westinghouse
service dealer.