Toshiba RAV-GM802ATW-E Installation Manual page 32

Table of Contents

Advertisement

[2] Minimum floor area: Amin (m
Total
Floor
Wall
refrigerant
standing
mounted
quantity*
unit
unit
h
0.6
1.8
0
M (kg)
Amin (m
2
)
1.90
30.98
3.44
1.94
32.13
3.57
1.97
33.30
3.70
2.01
34.49
3.83
2.04
35.71
3.97
2.08
38.94
4.10
2.11
38.20
4.24
2.15
39.48
4.39
2.18
40.78
4.53
2.22
42.10
4.68
GM80
2.25
43.44
4.83
GM90
2.29
44.80
4.98
2.32
48.18
5.13
2.36
47.59
5.29
2.39
49.01
5.45
2.43
50.48
5.61
2.46
51.93
5.77
2.50
53.41
5.93
2.53
54.92
6.10
2.57
56.45
6.27
Max 2.60
58.00
6.44
61-EN
)
2
Ceiling
Total
Floor
mounted
refrigerant
standing
mounted
unit
quantity*
unit
2.2
h
0.6
0
M (kg)
Amin (m
2.30
2.40
49.42
2.39
2.44
51.09
2.48
2.48
52.77
2.57
2.52
54.49
2.66
2.56
56.23
2.75
2.60
58.00
2.84
2.64
59.80
2.94
2.68
61.63
3.03
2.72
63.48
3.13
2.76
65.36
3.23
2.60
67.27
3.33
2.84
69.21
3.44
2.88
71.17
3.54
2.92
73.16
3.65
2.96
75.18
GM110
3.75
GM140
3.00
77.22
GM160
3.86
3.04
79.30
3.97
3.08
81.40
4.09
3.12
83.53
4.20
3.16
85.68
4.31
3.20
87.86
3.24
90.07
3.28
92.31
3.32
94.58
3.38
96.87
3.40
99.19
3.44
101.54
3.48
103.91
3.52
106.32
3.56
108.75
Max 3.60
111.20
* Total refrigerant quantity: Refrigerant quantity
precharged at factory + Additional refrigerant
quantity charged during installation.
– 31 –
A
Wall
Ceiling
min
mounted
120
unit
unit
1.8
2.2
2
)
110
5.49
3.68
5.68
3.80
100
5.86
3.93
6.05
4.05
6.25
4.18
90
6.44
4.31
6.64
4.45
6.85
4.58
80
7.05
4.72
7.26
4.86
70
7.47
5.00
7.69
5.15
7.91
5.29
60
8.13
5.44
8.35
5.59
8.58
5.74
50
8.81
5.90
9.04
6.05
40
9.28
8.21
9.52
6.37
9.76
6.54
30
10.01
8.70
10.26
6.87
10.51
7.03
20
10.76
7.21
11.02
7.38
10
11.28
7.55
11.55
7.73
11.81
7.91
0
12.08
8.09
1.80
12.38
8.27
[m
2
]
2.00
2.20
2.40
2.60
2.80
m[kg]
* The minimum floor area may differ from the stated value depending on the
parts mounted on the indoor unit and the control content of the indoor unit.
Be sure to check the installation manual of the indoor unit.
3.00
3.20
3.40
3.60
62-EN