Toshiba RAV-GM802ATW-E Installation Manual page 17

Table of Contents

Advertisement

■ Refrigerant pipe length
Single
Allowable pipe length (m)
Outdoor unit
Total length
Minimum
GM80,GM90
5
GM110,GM140,GM160
Pipe diameter (mm)
Outdoor unit
Gas side
GM80,GM90
15.9
GM110,GM140,GM160
Figure of single
Outdoor unit
Simultaneous twin
Allowable pipe length (m)
Total length
Branch piping
Outdoor unit
+ ℓ
1
2
2
+ ℓ
1
3
3
Maximum
Maximum
GM110,GM140,
50
15
GM160
Main pipe
Outdoor unit
Gas side
GM110
15.9
GM140,GM160
15.9
Figure of simultaneous twin
Outdoor unit
31-EN
Height difference (m)
Indoor-outdoor H
Maximum
Indoor unit: Upper
50
30
Number of bent portions
Liquid side
9.5
10 or less
Indoor unit
Height difference (m)
Indoor-outdoor H
Branch piping
- ℓ
3
2
Indoor unit:
Outdoor unit:
Maximum
Upper
Upper
10
30
30
Pipe diameter (mm)
Branch piping
Liquid side
Gas side
Liquid side
9.5
12.7
6.4
9.5
15.9
9.5
Indoor unit
Indoor unit
Simultaneous triple
Outdoor unit
Outdoor unit: Upper
GM160
30
Outdoor unit
GM160
Indoor-indoor
(∆h)
0.5
Number of bent
portions
10 or less
10 or less
– 16 –
Allowable pipe length (m)
Total length
Branch piping
Branch piping
+ ℓ
- ℓ
1
2
2
3
2
+ ℓ
- ℓ
1
3
3
4
2
+ ℓ
- ℓ
1
4
4
4
3
Maximum
Maximum
Maximum
50
15
10
Pipe diameter (mm)
Main pipe
Gas side
Liquid side
Gas side
15.9
9.5
12.7
Figure of Simultaneous triple
Indoor unit
Indoor unit
Outdoor unit
4
2
Distributor
1
Height difference (m)
Indoor-outdoor H
Indoor-indoor
(∆h)
Indoor unit:
Outdoor unit:
Upper
Upper
30
30
0.5
Number of bent
Branch pipe
portions
Liquid side
6.4
10 or less
Indoor unit
3
32-EN