Toshiba RAV-GM802ATW-E Installation Manual page 22

Table of Contents

Advertisement

How to wire
• Connect the indoor/outdoor connecting wires to the
terminal as identified with their respective numbers on
the terminal block of the indoor and outdoor units.
H07 RN-F or 60245 IEC 66 (1.5 mm
2
or more)
• When connecting the indoor/outdoor connecting wires
to the outdoor unit terminal, prevent water from
coming into the outdoor unit.
• Insulate the unsheathed cords (conductors) with
electrical insulation tape. Process them so that they
do not touch any electrical or metal parts.
• For interconnecting wires, do not use a wire joined to
another on the way. Use wires long enough to cover
the entire length.
• Wiring connections differ in conformance to EMC
standards, depending on whether the system is twin.
Connect wires according to respective instructions.
• Fix the indoor/outdoor connecting wires and power
supply wire with the supplied cord clamps or cable
ties.
<GM80, GM90>
• Fix the wires securely with the supplied cord clamps.
<GM110, GM140, GM160>
• Fix each wire tightly to the valve fixing plate with the cable
tie specified below. Measure the diameter of the wire to
be fixed, and fasten the wire with the supplied cable tie
(T50R-HSW from HellermannTyton) so that length A of the
surplus portion of the tie satisfies the following expression:
A = L
- L
1
2
A: Minimum length of surplus portion of cable tie (mm)
L
: Cable tie length (183mm for T50R-HSW)
1
L
: Circumferential length of wire (mm)
2
L
: Diameter of wire D (mm) × π
2
• Cut off the tie surplus portion (A) of the cable tie.
Flame
Model
Material
retardant
Manufacturer
grade
T50R-HSW
Nylon 66
UL94V-2
Cable tie
Valve fixing plate
Wires
CAUTION
• An installation fuse must be used for the power supply
line of this air conditioner.
• Incorrect / incomplete wiring may lead to an electrical
fire or smoke.
• Prepare a dedicated power supply for the air
conditioner.
41-EN
<GM80, GM90>
Terminal block
1
2
3
L
Screw
Indoor/outdoor
connecting wires
Stripping length power supply wire and
indoor/outdoor connecting wires
Earth wire
(mm)
Indoor/outdoor
connecting wires
Screw size and tightening torque
Screw
size
Hellermann
Power supply wire
Tyton
Indoor / Outdoor
M4
connecting wire
Earth screw
– 21 –
<GM1102ATW, GM1402ATW, GM1602ATW>
<Single-phase model>
N
Earth
screw
Cord clamp
Power supply
wire
Earth wire
Stripping length power supply wire and
Power supply
indoor/outdoor connecting wires
wire
80
Tightening
torque
(N•m)
Earth wire
1.2 to 1.4
Screw size and tightening torque
Power supply wire
Earth screw for
power supply wire
Indoor / Outdoor
connecting wire
Earth screw for
Indoor / Outdoor
connecting wire
To indoor unit
Power supply
terminal block
terminal block
Valve fixing
plate
Cable tie
Power supply wire
Indoor/outdoor
connecting wires
60
(mm)
Earth wire
Power supply
Indoor/outdoor
wire
connecting wires
Screw
Tightening
size
torque (N•m)
M6
2.5 to 3.0
M4
1.2 to 1.4
<GM1102AT8W, GM1402AT8W, GM1602AT8W>
<Three-phase model>
To indoor unit
Power supply
terminal block
terminal block
Earth
screw
Valve fixing
plate
Cable tie
Power supply wire
Indoor/outdoor
connecting wires
Stripping length power supply wire and
indoor/outdoor connecting wires
10
1
2 3
10
L1 L2 L3 N
10
10
80
50
80
60
60
(mm)
(mm)
Earth wire
Earth line
Indoor/outdoor
Power supply
connecting wires
wire
Screw size and tightening torque
Screw
Tightening
size
torque (N•m)
Power supply wire
M4
1.2 to 1.4
Earth screw for
M6
2.5 to 3.0
power supply wire
Indoor / Outdoor
connecting wire
M4
1.2 to 1.4
Earth screw for
Indoor / Outdoor
connecting wire
40
42-EN