How to check the snow guard fan control
You can check whether the snow guard fan control are enabled.
1. Check that the LED displays are placed in their initial status. If not, place them in the initial status.
2. Hold down SW01 for at least 5 seconds, and check that D804 flashes slowly. (Fig. 18)
3. Press SW01 twice to set the LED displays (D800 to D805) to the "LED displays for snow guard fan control"
shown below. If the setting is enabled, D801 lights and D804 and D805 flash rapidly. (Fig. 19)
4. Hold down SW01 and SW02 simultaneously for at least 5 seconds to return the LED displays to the initial status.
(Fig. 18)
LED displays Indicated when step 3 Is taken
D800
D801
D802
D803
D804
: ON, : OFF, : Slow flashing
When restoring the factory defaults
To restore the factory defaults in situations such as when relocating the units, follow the steps below.
1. Check that the LED displays are placed in their initial status. If not, place them in the initial status.
2. Hold down SW01 for at least 5 seconds, and check that D804 flashes slowly. (Fig. 20)
3. Push SW01 several times until the LED reaching to the "LED displays restored to factory defaults"
shown below. (Fig. 21)
(Fig. 20)
LED displays Indicated when step 2 Is taken
D800
D801
D802
D803
D804
: ON, : OFF, : Slow flashing
4. Hold down SW02 for at least 5 seconds, and check that D804 flashes slowly. (Fig. 22)
5. Hold down SW01 and SW02 simultaneously for at least 5 seconds to return the LED displays to the initial status.
(Fig. 22)
LED displays Indicated when step 4 Is taken
D800
D801
D802
D803
D804
: ON, : OFF, : Slow flashing
55-EN
(Fig. 19)
LED displays for snow guard fan control
D805
D800
D801
D802
D803
: ON, : OFF,
: Rapid flashing
(Fig. 21)
LED displays restored to factory defaults
D805
D800
D801
D802
D803
: ON, : OFF,
: Rapid flashing
D805
■ Night operation (Sound reduction)
• The air conditioner can be used in Night operation (Sound reduction) mode by connecting a commercially
available timer (to be procured locally) and a separately sold option "Application Control Kit (TCB-PCOS1E2)".
For details, refer to the operating instructions for the separately sold option "Application Control Kif'.
• The air conditioner can be operated in capacity saving mode to reduce the operation noise at night.
• Performance may lower depending on the outdoor air temperature, etc.
■ How to set the noise level in Night operation (Sound reduction)
mode
D804
D805
You can set DIP switches to select the noise level in Night operation (Sound reduction) mode(*1)(*2).
1. Make sure of the color (green or black) of the DIP switches (SW01) on the PC board.
2. Referring to the table below, set the DIP switches for the desired noise level.
*1 Night Operation limits the outdoor fan and compressor revolution speed, leading to a decrease in capacity.
*2 Depending on the remote controller to be connected, the same setting can be made from the remote controller.
For details, refer to the Installation manual of the remote controller, If different level settings are set from both the
Application Control Kit and the remote controller the quieter setting is prioritized.
Application Control Kit
P.C. board
D804
D805
DIP switches (SW01)
– 28 –
SPL : Sound Pressure Level
SW01 selects the noise level in Night operation (Sound reduction) mode.
Noise
Outdoor operation noise SPL
SW01 setting(*3)
level
(dB(A))
(switch color:green)
cooling
heating
GM80
42
44
GM90
44
44
level 1
GM110
40
43
GM140
42
46
GM160
43
45
cooling
heating
GM80
43
50
GM90
49
50
level 2
GM110
43
46
GM140
47
48
GM160
48
49
cooling
heating
GM80
49
51
GM90
50
51
level 3
GM110
47
49
GM140
52
53
GM160
54
55
*3 Don't do any switch settings except above. It would be the cause of the malfunction.
SW01 setting(*3)
(switch color:black)
OPEN
ON
OPEN
ON
OPEN
ON
56-EN