Emerson Rosemount 3051HT Quick Start Manual page 14

Hygienic pressure transmitter
Hide thumbs Also See for Rosemount 3051HT:

Advertisement

Quick Start Guide
2. Set damping: Device Settings → Setup Overview → Output.
3. Set process variables:
4. Set range values: Device Settings → Setup Overview → Output.
5. Set tag: Device Settings → Setup Overview → Device.
6. Set transfer function: Device Settings → Setup Overview → 
Output.
7. Set units:
2.4.1  Wireless configuration via Bluetooth
Download AMS Device Configurator
Procedure
Download and install the app from your app store. The first time
opening AMS Device Configurator, you may be asked to allow the
application to access media on your device and to access your
device's location. If prompted, select Allow.
Related information
Emerson.com/Automation-Solutions-Bluetooth
2.4.2  Configure via Bluetooth
Procedure
1. Launch AMS Device Configurator.
See
2. Select the device where you want to connect.
3. On first connection, enter the key for selected device.
4. At the top left, select the menu icon to navigate the desired
device menu.
14
Primary variable: Device Settings → Setup Overview → 
Output
Secondary/Tertiary/Quaternary variables: Device Settings 
→ Communication → HART → Variable Mapping
Pressure units: Device Settings → Setup Overview → 
Output
Other units: Device Settings → Output → Pressure/Flow/
Totalizer/Level/Volume/Module Temperature → Setup
AMS Device Configurator for Emerson Field
technology
®
wireless technology
®
July 2023
Devices.
Emerson.com/Rosemount