For The Installer - Scotsman FME2400RH Service Manual

Scotsman fme2400rh ice machine: user guide
Table of Contents

Advertisement

FOR THE INSTALLER

Select the Location:
The unit can only be installed indoors
within the limitations described on
page 2.
The ice machine will have to be
connected to the building's R-404A
refrigeration system, check to be
sure that the system has enough
extra capacity to handle a minimum
of additional 16,000 BTU's per hour
0
@ 110
F. liquid line temperature
0
(assume a 0
F. evaporator
temperature).
Storage Bin:
Scotsman's B90 will be the
presumed bin of choice. If using the
bin extension BX87, install heavy
duty leg kit KLP4 and place the bin
into position.
Remove the paper tape from the bin
edge gasket, and install the bin
extension onto the B90.
Remove the paper tape from the bin
extension top edge, and using a
mechanical lift, install the
FME2400RH onto the top of the
storage bin assembly.
Fasten the ice machine to the bin
using (4) 5/15-18 2.5" cap screws.
Level the assembly by:
a. Turning the leg levelers in or out
on the standard legs.
b. Use shims under the heavy duty
legs of the KLP4.
Locate the Nameplate: The
nameplate is located on the back
panel of the machine, and contains
the electrical characteristics
particular to the unit being installed.
Refrigeration Installation:
The skills of a refrigeration technician are required
to connect the ice machine to the buildings
refrigeration system.
TYPICAL INSTALLATION: ALLOW ROOM FOR SERVICE ACCESS
Local Codes must be observed.
A P-trap should be installed where there will be
more than 10' of vertical rise in the suction line.
January 1995
Page 3
FME2400RH
FME2400RH
BX87 BIN
EXTENSION
B90 STORAGE BIN

Advertisement

Table of Contents
loading

Table of Contents